Catalog PM 21 2013 - Siemens Industry, Inc.
Catalog PM 21 2013 - Siemens Industry, Inc.
Catalog PM 21 2013 - Siemens Industry, Inc.
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
© <strong>Siemens</strong> AG <strong>2013</strong><br />
SINAMICS S120 drive system<br />
Control Units<br />
CU320-2 Control Unit<br />
■ Technical specifications<br />
CU320-2 Control Unit<br />
PROFINET: 6SL3040-1MA01-0AA0<br />
PROFIBUS: 6SL3040-1MA00-0AA0<br />
Current requirement, max.<br />
1.0 A<br />
At 24 V DC,<br />
without taking account of digital outputs,<br />
expansion option slot and<br />
DRIVE-CLiQ supply<br />
Conductor cross-section, max. 2.5 mm 2<br />
Fuse protection, max.<br />
20 A<br />
Digital inputs<br />
In accordance with<br />
IEC 61131-2 type 1<br />
12 floating digital inputs<br />
8 bidirectional non-floating<br />
digital inputs/digital outputs<br />
• Voltage<br />
-3 … +30 V<br />
• Low level (an open digital input is -3 … +5 V<br />
interpreted as "low")<br />
• High level<br />
15 … 30 V<br />
• Current consumption at 24 V DC, typ. 9 mA<br />
• Delay time of<br />
digital inputs 1) , approx.<br />
-L → H 5 μs<br />
-H → L 50 μs<br />
• Conductor cross-section, max. 1.5 mm 2<br />
Digital outputs<br />
(sustained short-circuit strength)<br />
• Voltage<br />
• Load current per digital output, max.<br />
• Delay time 1) , typ./max.<br />
8 bidirectional non-floating<br />
digital outputs/digital inputs<br />
24 V DC<br />
500 mA<br />
-L → H 150 μs/400 μs<br />
-H → L 75 μs/100 μs<br />
• Conductor cross-section, max. 1.5 mm 2<br />
Power loss<br />
24 W<br />
PE connection<br />
M5 screw<br />
Ground connection<br />
M5 screw<br />
Dimensions<br />
• Width<br />
50 mm (1.97 in)<br />
•Height<br />
300 mm (11.8 in)<br />
•Depth<br />
226 mm (8.90 in)<br />
Weight, approx.<br />
2.3 kg (5 lb)<br />
Approvals, according to<br />
cULus<br />
■ Selection and ordering data<br />
Description<br />
Order No.<br />
CU320-2 PN Control Unit<br />
6SL3040-1MA01-0AA0<br />
Without CompactFlash card<br />
CU320-2 DP Control Unit<br />
6SL3040-1MA00-0AA0<br />
Without CompactFlash card<br />
Accessories<br />
Spacers<br />
6SL3064-1BB00-0AA0<br />
(2 units)<br />
For increasing the depth of the<br />
CU320-2 Control Unit to 270 mm (10.6 in)<br />
(if the integrated brackets are not used,<br />
but the depth still has to be 270 mm<br />
(10.6 in))<br />
STARTER commissioning tool 6SL3072-0AA00-0AG0<br />
Accessories for re-ordering<br />
SINAMICS/SINUMERIK/SIMOTION 6SL3066-4CA00-0AA0<br />
dust-proof blanking plugs<br />
(50 units)<br />
For DRIVE-CLiQ port<br />
3<br />
1) The specified delay times refer to the hardware. The actual reaction time<br />
depends on the time slice in which the digital input or output is processed.<br />
<strong>Siemens</strong> <strong>PM</strong> <strong>21</strong> · <strong>2013</strong><br />
3/<strong>21</strong>