Catalog PM 21 2013 - Siemens Industry, Inc.
Catalog PM 21 2013 - Siemens Industry, Inc.
Catalog PM 21 2013 - Siemens Industry, Inc.
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
SINAMICS S120 drive system<br />
Power Modules and line-side components<br />
Liquid-cooled Power Modules<br />
in chassis format<br />
■ Technical specifications (continued)<br />
© <strong>Siemens</strong> AG <strong>2013</strong><br />
3<br />
Line voltage<br />
Liquid-cooled Power Module in chassis format<br />
380 … 480 V 3 AC 6SL3315-1TE32-1AA3 6SL3315-1TE32-6AA3 6SL3315-1TE33-1AA3 6SL3315-1TE35-0AA3<br />
Output current<br />
• Rated current I rated A <strong>21</strong>0 260 310 490<br />
• Base-load current I L A 205 250 302 477<br />
• Base-load current I H A 178 233 277 438<br />
• For S6 duty (40 %) I S6 A 230 285 340 540<br />
• I max A 307 375 453 715<br />
Type rating 1)<br />
• Based on I rated kW (HP) 110 (150) 132 (200) 160 (250) 250 (400)<br />
• Based on I H kW (HP) 90 (150) 110 (150) 132 (200) 200 (350)<br />
Rated pulse frequency kHz 2 2 2 2<br />
Power loss, max.<br />
• Total, approx. kW 2.6 3.2 3.6 5.7<br />
• Lost to ambient air, approx. kW 0.06 0.07 0.09 0.14<br />
Cooling circuit<br />
• Rated volumetric flow<br />
for water at 70 kPa<br />
pressure drop<br />
dm 3 /min<br />
(l/min)<br />
9 9 12 12<br />
• Cooling circuit connection,<br />
inlet and return<br />
Pipe thread<br />
ISO 228-G ¾ B<br />
(external thread ¾''<br />
flat-sealing)<br />
Pipe thread<br />
ISO 228-G ¾ B<br />
(external thread ¾''<br />
flat-sealing)<br />
Pipe thread<br />
ISO 228-G ¾ B<br />
(external thread ¾''<br />
flat-sealing)<br />
• Liquid volume of integrated dm 3 (l) 0.52 0.52 0.88 0.88<br />
heat exchanger<br />
Sound pressure level<br />
dB 52 52 52 52<br />
L pA (1 m) at 50/60 Hz<br />
Rated input current A 230 285 340 540<br />
Current requirement<br />
at 24 V DC, max.<br />
A 1.4 1.4 1.5 1.5<br />
Line connection<br />
U1, V1, W1<br />
Flat connector<br />
for M12 screw<br />
Flat connector<br />
for M12 screw<br />
Flat connector<br />
for M12 screw<br />
Pipe thread<br />
ISO 228-G ¾ B<br />
(external thread ¾''<br />
flat-sealing)<br />
Flat connector<br />
for M12 screw<br />
• Conductor cross-section, max. mm 2 2 × 95 2 × 95 2 × 240 2 × 240<br />
DC link connection<br />
DCP, DCN<br />
Flat connector<br />
for M12 screw<br />
Flat connector<br />
for M12 screw<br />
Flat connector<br />
for M12 screw<br />
Flat connector<br />
for M12 screw<br />
• Conductor cross-section, max. mm 2 2 × 95 2 × 95 2 × 240 2 × 240<br />
Motor connection<br />
U2, V2, W2<br />
Flat connector<br />
for M12 screw<br />
Flat connector<br />
for M12 screw<br />
Flat connector<br />
for M12 screw<br />
Flat connector<br />
for M12 screw<br />
• Conductor cross-section, max. mm 2 2 × 95 2 × 95 2 × 240 2 × 240<br />
PE connection<br />
Flat connector<br />
for M12 screw<br />
Flat connector<br />
for M12 screw<br />
Flat connector<br />
for M12 screw<br />
Flat connector<br />
for M12 screw<br />
• Conductor cross-section, max. mm 2 2 × 95 2 × 95 2 × 240 2 × 240<br />
Motor cable length, max.<br />
• Shielded m (ft) 300 (984) 300 (984) 300 (984) 300 (984)<br />
• Unshielded m (ft) 450 (1476) 450 (1476) 450 (1476) 450 (1476)<br />
Degree of protection IP00 IP00 IP00 IP00<br />
Dimensions<br />
• Width mm (in) 265 (10.4) 265 (10.4) 265 (10.4) 265 (10.4)<br />
•Height mm (in) 835.5 (32.9) 835.5 (32.9) 983 (38.7) 983 (38.7)<br />
•Depth mm (in) 549 (<strong>21</strong>.6) 549 (<strong>21</strong>.6) 549 (<strong>21</strong>.6) 549 (<strong>21</strong>.6)<br />
Frame size FL FL GL GL<br />
Weight, approx. kg (lb) 77 (170) 77 (170) 108 (238) 108 (238)<br />
1) Nominal HP based on asynchronous (induction) motors and 460 V 3 AC. For specific sizing select drive based on motor nameplate current and overload.<br />
3/56 <strong>Siemens</strong> <strong>PM</strong> <strong>21</strong> · <strong>2013</strong>