© <strong>Siemens</strong> AG <strong>2013</strong><br />

SINAMICS S120 drive system<br />

Motor Modules<br />

Single Motor Modules in chassis format<br />

■ Technical specifications (continued)<br />

DC link voltage<br />

Single Motor Module in chassis format<br />

675 ... 1035 V DC<br />

6SL3320-1TG34-1AA3 6SL3320-1TG34-7AA3 6SL3320-1TG35-8AA3 6SL3320-1TG37-4AA3<br />

Output current<br />

• Rated current I rated A 410 465 575 735<br />

• Base-load current I L A 400 452 560 710<br />

• Base-load current I H A 367 416 514 675<br />

• I max A 600 678 840 1065<br />

Type rating 1)<br />

• Based on I rated kW 400 450 560 710<br />

• Based on I H kW 315 400 450 630<br />

Rated pulse frequency kHz 1.25 1.25 1.25 1.25<br />

Rated DC link current I 2)<br />

d<br />

when supplied via<br />

• Basic/Smart Line Module A 492 558 690 882<br />

• Active Line Module A 443 502 6<strong>21</strong> 794<br />

DC link capacitance μF 7400 7400 7400 11100<br />

Current requirement<br />

• At 24 V DC, max. A 1.0 1.0 1.0 1.25<br />

• Fan supply with 690 V 2 AC, A 2.1/3.1 2.1/3.1 2.1/3.1 3.1/4.6<br />

50/60 Hz, max.<br />

Power loss, max. kW 6.13 6.80 10.3 10.9<br />

Cooling air requirement m 3 /s (ft 3 /s) 0.78 0.78 0.78 1.08<br />

Sound pressure level<br />

L pA (1 m) at 50/60 Hz<br />

dB 70/73 70/73 70/73 71/73<br />

DC link connection<br />

DCP, DCN<br />

Motor connection<br />

U2, V2, W2<br />

Flat connector<br />

for busbar connection<br />

Flat connector<br />

for M12 screw<br />

Flat connector<br />

for busbar connection<br />

Flat connector<br />

for M12 screw<br />

Flat connector<br />

for busbar connection<br />

Flat connector<br />

for M12 screw<br />

Flat connector<br />

for busbar connection<br />

Flat connector<br />

for M12 screw<br />

• Conductor cross-section, max. mm 2 4 × 240 4 × 240 4 × 240 6 × 240<br />

PE connection M12 screw M12 screw M12 screw M12 screw<br />

• Conductor cross-section, max.<br />

- PE1/GND mm 2 1 × 240 1 × 240 1 × 240 1 × 240<br />

- PE2/GND mm 2 2 × 240 2 × 240 2 × 240 3 × 240<br />

Motor brake connection – – – –<br />

Motor cable length, max.<br />

(without external options)<br />

• Shielded m (ft) 300 (984) 300 (984) 300 (984) 300 (984)<br />

• Unshielded m (ft) 450 (1476) 450 (1476) 450 (1476) 450 (1476)<br />

Degree of protection IP00 IP00 IP00 IP00<br />

Dimensions<br />

• Width mm (in) 503 (19.8) 503 (19.8) 503 (19.8) 704 (27.7)<br />

•Height mm (in) 1475 (58.1) 1475 (58.1) 1475 (58.1) 1475 (58.1)<br />

•Depth mm (in) 540 (<strong>21</strong>.3) 540 (<strong>21</strong>.3) 540 (<strong>21</strong>.3) 540 (<strong>21</strong>.3)<br />

Frame size HX HX HX JX<br />

Weight, approx. kg (lb) 290 (639) 290 (639) 290 (639) 450 (992)<br />

3<br />

1) Rated power of a standard asynchronous (induction) motor at 690 V 3 AC.<br />

2) Rated DC link current for dimensioning an external DC connection.<br />

For DC link current calculation for dimensioning the Line Module, see chapter System description – Dimensioning.<br />

<strong>Siemens</strong> <strong>PM</strong> <strong>21</strong> · <strong>2013</strong><br />