Catalog PM 21 2013 - Siemens Industry, Inc.
Catalog PM 21 2013 - Siemens Industry, Inc.
Catalog PM 21 2013 - Siemens Industry, Inc.
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
SINAMICS S120 drive system<br />
Supplementary system components<br />
VSM10 Voltage Sensing Module<br />
© <strong>Siemens</strong> AG <strong>2013</strong><br />
■ Overview<br />
■ Technical specifications<br />
3<br />
The VSM10 Voltage Sensing Module can detect the exact line<br />
voltage characteristic and supports fault-free operation of Line<br />
Modules when power supply conditions are unfavorable, e.g.<br />
with severe voltage fluctuations or short-time interruptions.<br />
The phase differential voltage can be measured, either<br />
grounded (in the delivery state with jumper plugged in) or<br />
isolated.<br />
The VSM10 Voltage Sensing Module is integrated in chassis<br />
format Active Interface Modules and in the chassis format Smart<br />
Line Modules. It can be used optionally with all booksize format<br />
Active Line Modules and 16 kW, 36 kW, or 55 kW Smart Line<br />
Modules.<br />
VSM10 Voltage Sensing Module<br />
6SL3053-0AA00-3AA1<br />
Current requirement<br />
0.2 A<br />
at 24 V DC, max.<br />
• Conductor cross-section, max. 2.5 mm 2<br />
Power loss<br />
< 10 W<br />
Line voltage detection<br />
• Insulation resistance, neutral point – > 10 MΩ<br />
ground when the jumper is not inserted:<br />
• Input resistance<br />
- Terminal X5<strong>21</strong> > 362 kΩ/phase<br />
- Terminal X522 > 2.5 MΩ/phase<br />
Analog inputs<br />
(reserved for monitoring an<br />
Active Interface Module<br />
in chassis format)<br />
• Internal resistance, approx.<br />
100 kΩ<br />
(between differential inputs)<br />
• Resolution<br />
12 bit<br />
PE connection<br />
M4 screw<br />
Dimensions<br />
• Width<br />
50 mm (1.97 in)<br />
•Height<br />
150 mm (5.90 in)<br />
•Depth<br />
111 mm (4.37 in)<br />
Weight, approx.<br />
0.9 kg (2 lb)<br />
Approvals, according to<br />
cULus<br />
■ Design<br />
The VSM10 Voltage Sensing Module has the following<br />
connections and interfaces:<br />
• 1 connection for direct line voltage detection up to 690 V<br />
• 1 connection for line voltage detection using voltage<br />
transformers, maximum voltage 100 V<br />
• 2 analog inputs (reserved for resonance monitoring in<br />
Active Interface Modules in chassis format)<br />
• 1 temperature sensor input (KTY84-130 or PTC)<br />
• 1 DRIVE-CLiQ socket<br />
• 1 connection for the electronics power supply via the<br />
24 V DC power supply connector<br />
• 1 plug-in jumper for either grounded<br />
(delivery state) or isolated measurement<br />
• 1 PE (protective earth) connection<br />
The VSM10 Voltage Sensing Module can be snapped onto a<br />
TH 35 top-hat rail in accordance with EN 60715 (IEC 60715).<br />
The status of the VSM10 Voltage Sensing Module is indicated by<br />
a two-color LED.<br />
■ Selection and ordering data<br />
Description<br />
VSM10 Voltage Sensing Module<br />
Without DRIVE-CLiQ cable<br />
Order No.<br />
6SL3053-0AA00-3AA1<br />
3/236 <strong>Siemens</strong> <strong>PM</strong> <strong>21</strong> · <strong>2013</strong>