SINAMICS S120 drive system<br />
Line Modules and line-side components<br />
Basic Line Modules in booksize format<br />
■ Characteristic curves (continued)<br />
Braking power with external braking resistor<br />
The following load cycles are defined for the braking modules of<br />
the 20 kW and 40 kW Basic Line Modules:<br />
P<br />
2 x<br />
P rated<br />
1.5 x<br />
P rated<br />
G_D<strong>21</strong>1_EN_00185a<br />
Power P<br />
40<br />
kW<br />
30<br />
20<br />
G_D<strong>21</strong>1_EN_00187a<br />
3<br />
10<br />
P d<br />
3 s 46 s<br />
300 s<br />
t<br />
35<br />
The maximum possible braking power P max is calculated using<br />
the following formula:<br />
P max = U 2 /R<br />
U = Activation threshold<br />
R = Resistance value of the external braking resistor<br />
The maximum braking power is achieved with the smallest<br />
permissible resistance value. The maximum possible braking<br />
power falls at larger resistance values.<br />
0<br />
15<br />
20<br />
25<br />
Braking power of the 20 kW Basic Line Modules depending on the connected<br />
braking resistor<br />
When the recommended braking resistor is used, the following<br />
values result for the maximum braking power or continuous<br />
braking power:<br />
Braking resistor 6SE7023-2ES87-2DC0<br />
Resistance value = 20 Ω → max. braking power = 30 kW;<br />
continuous braking power = 5 kW<br />
30<br />
Max. braking power<br />
continuous braking power<br />
40<br />
Resistance<br />
Ω 45<br />
Power P<br />
80<br />
kW<br />
60<br />
G_D<strong>21</strong>1_EN_00188a<br />
40<br />
20<br />
0<br />
7.5 10 12.5 15 17.5 20 Ω 22.5<br />
Max. braking power<br />
continuous braking power<br />
Resistance<br />
Braking power of the 40 kW Basic Line Modules depending on the connected<br />
braking resistor<br />
When the recommended braking resistor is used, the following<br />
values result for the maximum braking power or continuous<br />
braking power:<br />
Braking resistor 6SE7028-0ES87-2DC0<br />
Resistance value = 8 Ω → max. braking power = 75 kW;<br />
continuous braking power = 10 kW (limited by braking module)<br />
<strong>Siemens</strong> <strong>PM</strong> <strong>21</strong> · <strong>2013</strong><br />
3/69