SINAMICS S120 drive system<br />

Motor Modules<br />

Single Motor Modules in booksize format<br />

■ Characteristic curves (continued)<br />

Derating characteristics<br />

© <strong>Siemens</strong> AG <strong>2013</strong><br />

3<br />

Permissible output current<br />

100<br />

%<br />

90<br />

80<br />

70<br />

60<br />

50<br />

40<br />

30<br />

20<br />

G_D<strong>21</strong>2_EN_00002c<br />

10<br />

0 2 4 6 8 10 12 14 16 kHz 20<br />

Pulse frequency<br />

Permissible output current<br />

100<br />

%<br />

95<br />

90<br />

85<br />

80<br />

75<br />

70<br />

65<br />

G_D<strong>21</strong>1_EN_00090a<br />

60<br />

0 1000 2000 3000 m 4000<br />

(3281) (6562) (9843) (ft) (13124)<br />

Installation altitude above sea level<br />

Output current dependent on pulse frequency<br />

(rated current up to 132 A for Single Motor Modules in booksize format)<br />

Output current as a function of installation altitude<br />

100<br />

G_D<strong>21</strong>1_EN_00006b<br />

1.0<br />

zulässiger Ausgangsstrom<br />

100<br />

%<br />

90<br />

80<br />

70<br />

60<br />

50<br />

40<br />

30<br />

20<br />

G_D<strong>21</strong>1_DE_00272<br />

10<br />

0 2 4 6 8 10 12 14 16 kHz 20<br />

Pulsfrequenz<br />

Permissible input voltage in %<br />

of rated voltage<br />

90<br />

0.9<br />

80<br />

0.8<br />

70<br />

0.7<br />

0 1000 2000 3000 m 4000<br />

(3281) (6562) (9843) (ft) (13124)<br />

Installation altitude above sea level<br />

Derating factor k U<br />

Output current dependent on pulse frequency<br />

(rated current up to 200 A for Single Motor Modules in booksize format)<br />

Permissible output current<br />

100<br />

%<br />

90<br />

80<br />

70<br />

G_D<strong>21</strong>1_EN_00089a<br />

60<br />

30 35 40 45 50 °C 55<br />

(86) (95) (104) (113) (122) (°F) (131)<br />

Ambient temperature<br />

Voltage derating dependent on installation altitude<br />

Permissible output current<br />

I rated, I H, I S6, I max<br />

100<br />

%<br />

75<br />

50<br />

25<br />

0<br />

0<br />

5 10 15 Hz (20...1600)<br />

Output frequency<br />

Current derating dependent on output frequency<br />

G_D<strong>21</strong>1_EN_00249a<br />

Output current dependent on ambient temperature<br />

3/152 <strong>Siemens</strong> <strong>PM</strong> <strong>21</strong> · <strong>2013</strong>