© <strong>Siemens</strong> AG <strong>2013</strong><br />
SINAMICS S120 drive system<br />
Line Modules and line-side components<br />
Active Line Modules in chassis format<br />
■ Technical specifications (continued)<br />
Line voltage<br />
380 ... 480 V 3 AC<br />
Feed/feedback power<br />
Active Line Module in chassis format<br />
6SL3330-7TE32-1AA3 6SL3330-7TE32-6AA3 6SL3330-7TE33-8AA3 6SL3330-7TE35-0AA3<br />
• Rated power P rated<br />
- At 400 V 3 AC<br />
- At 460 V 3 AC 2) kW<br />
(HP)<br />
132<br />
(200)<br />
• P max kW 198 240 352.5 450<br />
DC link current 1)<br />
• Rated current I rated_DC A 235 291 425 549<br />
• I H_DC A 209 259 378 489<br />
• I max_DC A 352 436 637 823<br />
Input current<br />
• Rated current<br />
A <strong>21</strong>0 260 380 490<br />
at 400 V 3 AC<br />
•Maximum A 315 390 570 735<br />
Current requirement<br />
• 24 V DC electronics<br />
A 1.1 1.1 1.35 1.35<br />
power supply, max.<br />
•Fan supply<br />
A 0.63/0.95 1.13/1.7 1.8/2.7 1.8/2.7<br />
with 400 V 2 AC, 50/60 Hz,<br />
max.<br />
DC link capacitance μF 4200 5200 7800 9600<br />
Power loss, max. kW 2.3 2.9 4.2 5.1<br />
Cooling air requirement m 3 /s (ft 3 /s) 0.17 (6.00) 0.23 (8.12) 0.36 (12.7) 0.36 (12.7)<br />
Sound pressure level<br />
L pA (1 m) at 50/60 Hz<br />
dB 64/67 64/67 69/73 69/73<br />
Line connection<br />
U1, V1, W1<br />
Flat connector for<br />
M10 screw<br />
160<br />
(225)<br />
Flat connector for<br />
M10 screw<br />
235<br />
(350)<br />
Flat connector for<br />
M10 screw<br />
• Conductor cross-section, max. mm 2 2 × 185 2 × 185 2 × 240 2 × 240<br />
DC link connection<br />
DCP, DCN<br />
Flat connector for<br />
M10 screw<br />
Flat connector for<br />
M10 screw<br />
Flat connector for<br />
M10 screw<br />
300<br />
(450)<br />
Flat connector for<br />
M10 screw<br />
Flat connector for<br />
M10 screw<br />
• Conductor cross-section, max. mm 2 2 × 185 2 × 185 2 × 240 2 × 240<br />
PE connection M10 screw M10 screw M10 screw M10 screw<br />
• Conductor cross-section, max.<br />
- PE1/GND mm 2 1 × 185 1 × 185 1 × 240 1 × 240<br />
- PE2/GND mm 2 2 × 185 2 × 185 2 × 240 2 × 240<br />
Cable length, max.<br />
(total of all motor power cables<br />
and DC link)<br />
• Shielded m (ft) 2700 (8859) 2700 (8859) 2700 (8859) 2700 (8859)<br />
• Unshielded m (ft) 4050 (13288) 4050 (13288) 4050 (13288) 4050 (13288)<br />
Degree of protection IP20 IP20 IP20 IP20<br />
Dimensions<br />
• Width mm (in) 326 (12.8) 326 (12.8) 326 (12.8) 326 (12.8)<br />
•Height mm (in) 1400 (55.1) 1400 (55.1) 1533 (60.3) 1533 (60.3)<br />
•Depth mm (in) 356 (14.1) 356 (14.1) 545 (<strong>21</strong>.5) 545 (<strong>21</strong>.5)<br />
Frame size FX FX GX GX<br />
Weight, approx. kg (lb) 95 (209) 95 (209) 136 (300) 136 (300)<br />
3<br />
1) With a rated DC link voltage = 1.5 × V line rated (example: 600 V = 1.5 × 400 V).<br />
2) Nominal HP ratings are provided for ease of assigning components only. The Line Module outputs are dependent on the Motor Module loading and are to be<br />
dimensioned accordingly.<br />
<strong>Siemens</strong> <strong>PM</strong> <strong>21</strong> · <strong>2013</strong><br />