Catalog PM 21 2013 - Siemens Industry, Inc.
Catalog PM 21 2013 - Siemens Industry, Inc.
Catalog PM 21 2013 - Siemens Industry, Inc.
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
SINAMICS S120 drive system<br />
Motor Modules<br />
Single Motor Modules in chassis format<br />
■ Technical specifications (continued)<br />
© <strong>Siemens</strong> AG <strong>2013</strong><br />
3<br />
DC link voltage<br />
675 ... 1035 V DC<br />
Output current<br />
Single Motor Module in chassis format<br />
6SL3320-1TG38-1AA3 6SL3320-1TG38-8AA3 6SL3320-1TG41-0AA3 6SL3320-1TG41-3AA3<br />
• Rated current I rated A 810 910 1025 1270<br />
• Base-load current I L A 790 880 1000 1230<br />
• Base-load current I H A 724 814 917 1136<br />
• I max A 1185 1320 1500 1845<br />
Type rating 1)<br />
• Based on I rated kW 800 900 1000 1200<br />
• Based on I H kW 710 800 900 1000<br />
Rated pulse frequency kHz 1.25 1.25 1.25 1.25<br />
Rated DC link current I d<br />
2)<br />
when supplied via<br />
• Basic/Smart Line Module A 972 1092 1230 1524<br />
• Active Line Module A 875 983 1107 1372<br />
DC link capacitance μF 11100 14400 14400 19200<br />
Current requirement<br />
• At 24 V DC, max. A 1.25 1.4 1.4 1.4<br />
• Fan supply with 690 V 2 AC,<br />
50/60 Hz, max.<br />
A 3.1/4.6 3.1/4.6 3.1/4.6 3.1/4.6<br />
Power loss, max. kW 11.5 11.7 13.2 16.0<br />
Cooling air requirement m 3 /s (ft 3 /s) 1.08 (38.1) 1.08 (38.1) 1.08 (38.1) 1.08 (38.1)<br />
Sound pressure level L pA<br />
(1 m)<br />
at 50/60 Hz<br />
dB 71/73 71/73 71/73 71/73<br />
DC link connection<br />
DCP, DCN<br />
Motor connection<br />
U2, V2, W2<br />
Flat connector<br />
for busbar connection<br />
Flat connector<br />
for M12 screw<br />
Flat connector<br />
for busbar connection<br />
Flat connector<br />
for M12 screw<br />
Flat connector<br />
for busbar connection<br />
Flat connector<br />
for M12 screw<br />
Flat connector<br />
for busbar connection<br />
Flat connector<br />
for M12 screw<br />
• Conductor cross-section, max. mm 2 6 × 240 6 × 240 6 × 240 6 × 240<br />
PE connection M12 screw M12 screw M12 screw M12 screw<br />
• Conductor cross-section, max.<br />
- PE1/GND mm 2 1 × 240 1 × 240 1 × 240 1 × 240<br />
- PE2/GND mm 2 3 × 240 3 × 240 3 × 240 3 × 240<br />
Motor brake connection – – – –<br />
Motor cable length, max.<br />
(without external options)<br />
• Shielded m (ft) 300 (984) 300 (984) 300 (984) 300 (984)<br />
• Unshielded m (ft) 450 (1476) 450 (1476) 450 (1476) 450 (1476)<br />
Degree of protection IP00 IP00 IP00 IP00<br />
Dimensions<br />
• Width mm (in) 704 (27.7) 704 (27.7) 704 (27.7) 704 (27.7)<br />
•Height mm (in) 1475 (58.1) 1475 (58.1) 1475 (58.1) 1475 (58.1)<br />
•Depth mm (in) 540 (<strong>21</strong>.3) 540 (<strong>21</strong>.3) 540 (<strong>21</strong>.3) 540 (<strong>21</strong>.3)<br />
Frame size JX JX JX JX<br />
Weight, approx. kg (lb) 450 (992) 450 (992) 450 (992) 450 (992)<br />
1) Rated power of a standard asynchronous (induction) motor at 690 V 3 AC.<br />
2) Rated DC link current for dimensioning an external DC connection.<br />
For DC link current calculation for dimensioning the Line Module, see chapter System description – Dimensioning.<br />
3/162 <strong>Siemens</strong> <strong>PM</strong> <strong>21</strong> · <strong>2013</strong>