SINAMICS S120 drive system<br />
Power Modules and line-side components<br />
Air-cooled Power Modules<br />
in chassis format<br />
■ Technical specifications (continued)<br />
© <strong>Siemens</strong> AG <strong>2013</strong><br />
3<br />
Line voltage<br />
Air-cooled Power Module in chassis format<br />
380 … 480 V 3 AC 6SL3310-<br />
1TE32-1AA3<br />
6SL3310-<br />
1TE32-6AA3<br />
6SL3310-<br />
1TE33-1AA3<br />
6SL3310-<br />
1TE33-8AA3<br />
6SL3310-<br />
1TE35-0AA3<br />
Output current<br />
• Rated current I rated A <strong>21</strong>0 260 310 380 490<br />
• Base-load current I L A 205 250 302 370 477<br />
• Base-load current I H A 178 233 277 340 438<br />
• For S6 duty (40 %) I S6 A 230 285 340 430 540<br />
• I max A 307 375 453 555 715<br />
Type rating 1)<br />
• Based on I rated kW (HP) 110 (150) 132 (200) 160 (250) 200 (300) 250 (400)<br />
• Based on I H kW (HP) 90 (150) 110 (150) 132 (200) 160 (250) 200 (350)<br />
Rated pulse frequency kHz 2 2 2 2 2<br />
Current requirement<br />
A 0.8 0.8 0.9 0.9 0.9<br />
with 24 V DC, max. 2)<br />
Power loss, max. kW 2.54 3.36 4.07 4.67 5.96<br />
Cooling air requirement m 3 /s (ft 3 /s) 0.17 (6.00) 0.23 (8.12) 0.36 (12.7) 0.36 (12.7) 0.36 (12.7)<br />
Sound pressure level<br />
dB 66/67 68/72 68/72 68/72 68/72<br />
L pA (1 m) at 50/60 Hz<br />
Rated input current A 229 284 338 395 509<br />
Line connection<br />
U1, V1, W1<br />
Flat connector for<br />
M10 screw<br />
Flat connector for<br />
M10 screw<br />
Flat connector for<br />
M10 screw<br />
Flat connector for<br />
M10 screw<br />
• Conductor cross-section, max. mm 2 2 × 185 2 × 185 2 × 240 2 × 240 2 × 240<br />
DC link connection<br />
DCPA, DCNA<br />
(option Braking Module)<br />
Flat connector for<br />
M8 screw<br />
Flat connector for<br />
M8 screw<br />
Flat connector for<br />
M8 screw<br />
Flat connector for<br />
M8 screw<br />
• Conductor cross-section, max. mm 2 1 × 35 1 × 35 1 × 50 1 × 50 1 × 50<br />
DC link connection<br />
DCPS, DCNS<br />
Flat connector for<br />
M8 screw<br />
Flat connector for<br />
M8 screw<br />
Flat connector for<br />
M8 screw<br />
Flat connector for<br />
M8 screw<br />
• Conductor cross-section, max. mm 2 1 × 35 1 × 35 1 × 70 1 × 70 1 × 70<br />
Motor connection<br />
U2, V2, W2<br />
Flat connector for<br />
M10 screw<br />
Flat connector for<br />
M10 screw<br />
Flat connector for<br />
M10 screw<br />
Flat connector for<br />
M10 screw<br />
Flat connector for<br />
M10 screw<br />
Flat connector for<br />
M8 screw<br />
Flat connector for<br />
M8 screw<br />
Flat connector for<br />
M10 screw<br />
• Conductor cross-section, max. mm 2 2 × 185 2 × 185 2 × 240 2 × 240 2 × 240<br />
PE connection<br />
Flat connector for<br />
M10 screw<br />
Flat connector for<br />
M10 screw<br />
Flat connector for<br />
M10 screw<br />
Flat connector for<br />
M10 screw<br />
Flat connector for<br />
M10 screw<br />
• Conductor cross-section, max. mm 2 2 × 185 2 × 185 2 × 240 2 × 240 2 × 240<br />
Motor cable length 3) , max.<br />
• Shielded m (ft) 300 (984) 300 (984) 300 (984) 300 (984) 300 (984)<br />
• Unshielded m (ft) 450 (1476) 450 (1476) 450 (1476) 450 (1476) 450 (1476)<br />
Degree of protection IP20 IP20 IP20 IP20 IP20<br />
Dimensions<br />
• Width mm (in) 326 (12.8) 326 (12.8) 326 (12.8) 326 (12.8) 326 (12.8)<br />
•Height mm (in) 1400 (55.1) 1400 (55.1) 1533 (60.3) 1533 (60.3) 1533 (60.3)<br />
•Depth mm (in) 356 (14.0) 4) 356 (14.0) 4) 549 (<strong>21</strong>.6) 549 (<strong>21</strong>.6) 549 (<strong>21</strong>.6)<br />
Frame size FX FX GX GX GX<br />
Weight, approx. kg (lb) 104 (229) 104 (229) 162 (357) 162 (357) 162 (357)<br />
1) Nominal HP based on asynchronous (induction) motors and 460 V 3 AC. For specific sizing select drive based on motor nameplate current and overload.<br />
2) Current consumption of Power Module only. If a Control Unit is supplied with 24 V DC over the Power Module, its current consumption must be added.<br />
3) Motor cable length, max. 100 m (328 ft) (shielded) in conjunction with a line filter to maintain the limit values of EN 61800-3 Category C2.<br />
4) Depth = 4<strong>21</strong> mm (16.6 in) including front cover when CU310-2/D410-2 Control Unit is installed.<br />
3/50 <strong>Siemens</strong> <strong>PM</strong> <strong>21</strong> · <strong>2013</strong>