Catalog PM 21 2013 - Siemens Industry, Inc.
Catalog PM 21 2013 - Siemens Industry, Inc.
Catalog PM 21 2013 - Siemens Industry, Inc.
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
SINAMICS S120 drive system<br />
Power Modules and line-side components<br />
Air-cooled Power Modules<br />
in blocksize format<br />
■ Technical specifications (continued)<br />
© <strong>Siemens</strong> AG <strong>2013</strong><br />
3<br />
Line voltage<br />
Air-cooled <strong>PM</strong>340 Power Module in blocksize format<br />
380 … 480 V 3 AC 6SL3<strong>21</strong>0-1SE31-1... 6SL3<strong>21</strong>0-1SE31-5... 6SL3<strong>21</strong>0-1SE31-8...<br />
Output current<br />
• Rated current I rated A 110 145 178<br />
• Base-load current I H A 95 115 155<br />
• For S6 duty (40 %) I S6 A 143 188 231<br />
• I max A 180 220 290<br />
Type rating 1)<br />
• Based on I rated kW (HP) 55 (75) 75 (100) 90 (125)<br />
• Based on I H kW (HP) 45 (60) 55 (75) 75 (100)<br />
Rated pulse frequency kHz 4 4 4<br />
Power loss kW 1.42 1.93 2.31<br />
Cooling air requirement m 3 /s (ft 3 /s) 0.094 (3.3) 0.094 (3.3) 0.117 (4.1)<br />
Sound pressure level L pA dB < 60 < 60 65<br />
(1 m)<br />
24 V DC power supply A 1.0 1.0 1.0<br />
for the Control Unit<br />
Rated input current 2) A 115/129 151/168 186/204<br />
with/without line reactor<br />
Resistance value<br />
Ω ≥ 8.2 ≥ 8.2 ≥ 8.2<br />
of the external braking resistor<br />
Cable length<br />
m (ft) 15 (49) 15 (49) 15 (49)<br />
to braking resistor, max.<br />
Line connection<br />
M8 screw stud M8 screw stud M8 screw stud<br />
U1/L1, V1/L2, W1/L3<br />
• Conductor cross-section, max. mm 2 120 120 120<br />
DC link connection,<br />
M8 screw stud M8 screw stud M8 screw stud<br />
connection for<br />
braking resistor<br />
DCP/R1, DCN, R2<br />
• Conductor cross-section, max. mm 2 120 120 120<br />
Motor connection<br />
M8 screw stud M8 screw stud M8 screw stud<br />
U2, V2, W2<br />
• Conductor cross-section, max. mm 2 120 120 120<br />
PE connection M8 screw M8 screw M8 screw<br />
Motor cable length 3) , max.<br />
• Shielded m (ft) 70 (230) 70 (230) 70 (230)<br />
• Unshielded m (ft) 100 (328) 100 (328) 100 (328)<br />
Degree of protection IP20 IP20 IP20<br />
Dimensions<br />
• Width mm (in) 350 (13.8) 350 (13.8) 350 (13.8)<br />
• Height <strong>PM</strong>340<br />
mm (in) 634/934 (25.0/36.8) 634/934 (25.0/36.8) 634/934 (25.0/36.8)<br />
without/with int. filter<br />
•Depth<br />
-<strong>PM</strong>340 mm (in) 315.5 (12.4) 315.5 (12.4) 315.5 (12.4)<br />
- <strong>PM</strong>340 with CU310-2/D410-2 mm (in) 405.1 (15.9) 405.1 (15.9) 405.1 (15.9)<br />
- <strong>PM</strong>340 with CUA31/CUA32 mm (in) 345.8 (13.6) 345.8 (13.6) 345.8 (13.6)<br />
Frame size FSF FSF FSF<br />
Weight, approx.<br />
<strong>PM</strong>340 without/with int. filter<br />
kg (lb) 50.7/66.7 (112/147) 50.7/66.7 (112/147) 50.7/66.7 (112/147)<br />
1) Nominal HP based on asynchronous (induction) motors and 460 V 3 AC. For specific sizing select drive based on motor nameplate current and overload.<br />
2) The input current depends on the motor load and line impedance.<br />
The input currents apply for rated power loading (based on I rated ) for a line impedance corresponding to u k = 1 %.<br />
3) Max. motor cable length 25 m (82 ft) (shielded) for <strong>PM</strong>340 Power Modules with integrated line filter to maintain the limit values of EN 61800-3 Category C2.<br />
3/36 <strong>Siemens</strong> <strong>PM</strong> <strong>21</strong> · <strong>2013</strong>