SINAMICS S120 drive system<br />

Line Modules and line-side components<br />

Active Line Modules in chassis format<br />

© <strong>Siemens</strong> AG <strong>2013</strong><br />

3<br />

■ Technical specifications (continued)<br />

Line voltage<br />

380 ... 480 V 3 AC<br />

Feed/feedback<br />

power<br />

• Rated power P rated<br />

- At 400 V 3 AC<br />

kW<br />

- At 460 V 3 AC 2) (HP)<br />

Active Line Module in chassis format<br />

6SL3330-<br />

7TE36-1AA3<br />

380<br />

(550)<br />

6SL3330-<br />

7TE37-5AA3<br />

450<br />

(600)<br />

6SL3330-<br />

7TE38-4AA3<br />

500<br />

(700)<br />

6SL3330-<br />

7TE41-0AA3<br />

630<br />

(800)<br />

6SL3330-<br />

7TE41-2AA3<br />

800<br />

(1000)<br />

6SL3330-<br />

7TE41-4AA3<br />

900<br />

(1150)<br />

• P max kW 570 675 750 945 1200 1350<br />

DC link current 1)<br />

• Rated current I rated_DC A 678 835 940 1103 1412 1574<br />

• I H_DC A 603 700 837 982 1255 1401<br />

• I max_DC A 1017 1252 1410 1654 <strong>21</strong>20 2361<br />

Input current<br />

• At 400 V 3 AC A 605 745 840 985 1260 1405<br />

•Maximum A 907 1117 1260 1477 1890 <strong>21</strong>07<br />

Current requirement<br />

• 24 V DC electronics<br />

A 1.4 1.4 1.4 1.5 1.7 1.7<br />

power supply, max.<br />

•Fan supply<br />

A 3.6 3.6 3.6 5.4 5.4 7.8<br />

with 400 V 2 AC, max.<br />

DC link capacitance μF 12600 15600 16800 18900 26100 28800<br />

Power loss, max. kW 6.6 7.7 8.2 10.8 13 14.2<br />

Cooling air requirement m 3 /s (ft 3 /s) 0.78 (27.5) 0.78 (27.5) 0.78 (27.5) 1.08 (38.1) 1.08 (38.1) 1.08 (38.1)<br />

Sound pressure level<br />

L pA (1 m) at 50/60 Hz<br />

dB 70/73 70/73 70/73 71/73 71/73 71/73<br />

Line connection<br />

U1, V1, W1<br />

Flat connector<br />

for M12 screw<br />

Flat connector<br />

for M12 screw<br />

Flat connector<br />

for M12 screw<br />

Flat connector<br />

for M12 screw<br />

Flat connector<br />

for M12 screw<br />

Flat connector<br />

for M12 screw<br />

• Conductor cross-section, max. mm 2 4 × 240 4 × 240 4 × 240 6 × 240 6 × 240 6 × 240<br />

DC link connection<br />

DCP, DCN<br />

Flat connector<br />

for busbar<br />

connection<br />

Flat connector<br />

for busbar<br />

connection<br />

Flat connector<br />

for busbar<br />

connection<br />

Flat connector<br />

for busbar<br />

connection<br />

Flat connector<br />

for busbar<br />

connection<br />

Flat connector<br />

for busbar<br />

connection<br />

PE connection M12 screw M12 screw M12 screw M12 screw M12 screw M12 screw<br />

• Conductor cross-section, max.<br />

- PE1/GND mm 2 1 × 240 1 × 240 1 × 240 1 × 240 1 × 240 1 × 240<br />

- PE2/GND mm 2 2 × 240 2 × 240 2 × 240 2 × 240 2 × 240 2 × 240<br />

Cable length, max.<br />

(total of all motor power cables<br />

and DC link)<br />

• Shielded m (ft) 3900 (12796) 3900 (12796) 3900 (12796) 3900 (12796) 3900 (12796) 3900 (12796)<br />

• Unshielded m (ft) 5850 (19194) 5850 (19194) 5850 (19194) 5850 (19194) 5850 (19194) 5850 (19194)<br />

Degree of protection IP00 IP00 IP00 IP00 IP00 IP00<br />

Dimensions<br />

• Width mm (in) 503 (19.8) 503 (19.8) 503 (19.8) 704 (27.7) 704 (27.7) 704 (27.7)<br />

•Height mm (in) 1475 (58.1) 1475 (58.1) 1475 (58.1) 1475 (58.1) 1475 (58.1) 1475 (58.1)<br />

•Depth mm (in) 540 (<strong>21</strong>.3) 540 (<strong>21</strong>.3) 540 (<strong>21</strong>.3) 540 (<strong>21</strong>.3) 540 (<strong>21</strong>.3) 540 (<strong>21</strong>.3)<br />

Frame size HX HX HX JX JX JX<br />

Weight, approx. kg (lb) 290 (639) 290 (639) 290 (639) 450 (992) 450 (992) 450 (992)<br />

1) With a rated DC link voltage = 1.5 × V line rated (example: 600 V = 1.5 × 400 V).<br />

2) Nominal HP ratings are provided for ease of assigning components only. The Line Module outputs are dependent on the Motor Module loading and are to be<br />

dimensioned accordingly.<br />

3/126 <strong>Siemens</strong> <strong>PM</strong> <strong>21</strong> · <strong>2013</strong>