SINAMICS S120 drive system<br />

Power Modules and line-side components<br />

Air-cooled Power Modules<br />

in chassis format<br />

© <strong>Siemens</strong> AG <strong>2013</strong><br />

■ Characteristic curves (continued)<br />

Derating factors<br />

3<br />

Output current dependent on pulse frequency<br />

Power Module<br />

Rated output Derating factor<br />

in chassis format current<br />

Type A for a pulse frequency<br />

of 4 kHz<br />

6SL3310-1TE32-1AA3 <strong>21</strong>0 0.82<br />

6SL3310-1TE32-6AA3 260 0.83<br />

6SL3310-1TE33-1AA3 310 0.88<br />

6SL3310-1TE33-8AA3 380 0.87<br />

6SL3310-1TE35-0AA3 490 0.78<br />

Permissible input voltage in %<br />

of rated voltage<br />

100<br />

90<br />

80<br />

G_D<strong>21</strong>1_EN_00006b<br />

1.0<br />

0.9<br />

0.8<br />

Derating factor k U<br />

1.3<br />

G_D<strong>21</strong>1_EN_00004c<br />

70<br />

0.7<br />

0 1000 2000 3000 m 4000<br />

(3281) (6562) (9843) (ft) (13124)<br />

Installation altitude above sea level<br />

Derating factor k T<br />

1.2<br />

1.1<br />

1.0<br />

0.9<br />

0.8<br />

20 25 30 35 40 45 50 °C 55<br />

(68) (77) (86) (95) (104) (113) (122)(°F)(131)<br />

Ambient temperature<br />

Current derating dependent on ambient temperature<br />

Note: A factor k T > 1 must be applied only in conjunction with<br />

current derating dependent on installation altitude, see chapter<br />

System description – Dimensioning.<br />

Voltage derating dependent on installation altitude<br />

Permissible output current<br />

I rated, I H, I S6, I max<br />

100<br />

%<br />

75<br />

50<br />

25<br />

0<br />

0<br />

5 10 15 Hz (20...1600)<br />

Output frequency<br />

Current derating dependent on output frequency<br />

G_D<strong>21</strong>1_EN_00249a<br />

100<br />

G_D<strong>21</strong>1_EN_00005b<br />

1.00<br />

Permissible continuous current in %<br />

of rated current<br />

95<br />

90<br />

0.95<br />

0.90<br />

85<br />

0.85<br />

0 1000 2000 3000 m 4000<br />

(3281) (6562) (9843) (ft) (13124)<br />

Installation altitude above sea level<br />

Derating factor k I<br />

Current derating dependent on installation altitude<br />

3/52 <strong>Siemens</strong> <strong>PM</strong> <strong>21</strong> · <strong>2013</strong>