4. SYSTEM DESCRIPTION<br />

4.3.3 Pumping factor<br />

The pumping factor is defined as the mass flow ratio <strong>of</strong> the weak solution<br />

<strong>and</strong> the refrigerant[18]:<br />

PF = ṁ55<br />

ṁ 51<br />

(4.3)<br />

For the st<strong>and</strong>ard configuration PF = 12,75. This number should not be<br />

too high since it increases the amount <strong>of</strong> LiBr solution circulated per kW<br />

<strong>of</strong> cooling which increases desorber heating, absorber cooling <strong>and</strong> pump<br />

power.<br />