7. DISCUSSION<br />

extract as much <strong>of</strong> the waste heat as it can, there will only be enough<br />

waste heat left to make 3kW <strong>of</strong> hot water per 100kW <strong>fuel</strong> input (see figure<br />

5.32 page 153). This means that almost all <strong>of</strong> the waste heat can be used<br />

in the ABS unit. So if domestic hot water heating is to be made from the<br />

SOFC exhaust gas then the cooling production will decrease a lot, <strong>and</strong> for<br />

each kW the hot water production is decreased, approximately 1,5kW <strong>of</strong><br />

cooling can be made (since COP ABS = 1,48).<br />

Hotel locations<br />

One <strong>of</strong> the really good places to use the SOFC-ABS would be at the<br />

Seychelles. First <strong>of</strong> all the primary industry for this group <strong>of</strong> isl<strong>and</strong>s is<br />

tourism so there are a lot <strong>of</strong> hotels. Secondly their primary energy source<br />

is oil which the government wants to replace which is an advantage for<br />

the SOFC. Thirdly the climate is perfect for using the ABS air conditioning:<br />

the average temperature is between 24 <strong>and</strong> 30 degrees all year, creating<br />

a certain need for air conditioning all year round. And since the<br />

average temperature rarely exceeds 33 ◦ C, the absorption unit is capable<br />

<strong>of</strong> running just about all the time with a desorber temperature <strong>of</strong> no more<br />

than 150 ◦ C which is the maximum ambient temperature that can be used<br />

with this desorber temperature is only 33 ◦ C since the relative humidity is<br />

around 80%.<br />

Bangkok could at first glance also be a potential place for the SOFC-ABS.<br />

The temperature is a couple <strong>of</strong> degrees higher than for the Seychelles during<br />

summer (increasing the air conditioning need). But since the maximum<br />

temperature is higher, <strong>and</strong> the climate is very humid (up to 90%<br />

relative humidity), the desorber temperature will have to be increased<br />

up to 190 ◦ C for the system to even run at this ambient temperature. So<br />

fairly expensive materials are likely to be needed in order to minimize<br />

the corrosion rate <strong>of</strong> the Desorber (<strong>and</strong> probably also SHEX), meaning<br />

that Bangkok after all might not be the best place to use the absorption<br />

cooling unit after all.<br />

Las Vegas has even higher maximum temperatures (up to 46 ◦ C), but since<br />

the air humidity is much lower than in Bangkok, the system will run at<br />

temperature up to 48 ◦ C at a desorber temperature <strong>of</strong> 150 ◦ C. So this makes<br />

for a much better place to put the SOFC-ABS unit - especially since there<br />

are a lot <strong>of</strong> hotels <strong>and</strong> casinos which needs air condition <strong>and</strong> electricity.<br />

Although in this climate, the water consumption could be a problem.<br />

174