6. CASES AND ECONOMICS<br />

Data from Bangkok is shown in figure 6.3 to illustrate the climate <strong>of</strong><br />

the middle part the country. The relative humidity varies a lot <strong>and</strong> is<br />

more extreme than in the Seychelles: The relative humidity is up to 94% 2 ,<br />

<strong>and</strong> the temperature is normally in the range <strong>of</strong> 20-35 ◦ C but can be as<br />

high as 41 ◦ C.<br />

Figure 6.3: Weather data for Bangkok, Thail<strong>and</strong>. Average condition. Table taken from [3].<br />

Keeping these climate data in mind, the COP <strong>of</strong> the system (blue<br />

line with round dots in figure 6.4A) shows that it is not sufficient to<br />

use a desorber temperature (DES2) <strong>of</strong> 150 ◦ C since COP ABS,f uel decreases<br />

drastically at about 30 ◦ C. Thus it has been necessary to increase T DES2 3 in<br />

order to extend the range <strong>of</strong> the ambient temperature at which the system<br />

can operate (blue line with triangular markers in figure 6.4A). When the<br />

temperature <strong>of</strong> DES2 is increased, the ambient temperature can be up to<br />

about 40 ◦ C, but the high ambient temperature does significantly decrease<br />

COP ABS .<br />

The biggest problem though is that DES2 is exposed to a temperature<br />

<strong>of</strong> up to 190 ◦ C which is much higher than the recommended maximum<br />

temperature <strong>of</strong> 150 ◦ C according to [27] (see brown curve market with<br />

triangles in figure 6.4B). Thus it should not be expected that a st<strong>and</strong>ard<br />

absorption unit can operate under this high temperature due to corrosion<br />

problems.<br />

2 The most extreme values <strong>of</strong> the humidity is likely to be caused by fluctuating<br />

temperature, so it is assumed that the humidity is not above 0,9 during daytime.<br />

3 The desorber temperature <strong>of</strong> DES1 has been changed as well since its optimum<br />

value depends on the temperature <strong>of</strong> DES2.<br />

158