“<strong>Kozloduy</strong> <strong>NPP</strong>” PLC<br />

SUMMARY REPORT<br />

<strong>for</strong> <strong>Conduct</strong> <strong>of</strong> <strong>Kozloduy</strong> <strong>NPP</strong><br />

<strong>Stress</strong> <strong>Tests</strong><br />

etc. They all are located at elevation over 0,00, which means that they cannot be flooded in terms <strong>of</strong><br />

flooding.<br />

1.3.2.6.4 Alternative options to recharge the batteries<br />

Maintaining and extension <strong>of</strong> battery operability can be provided in two ways:<br />

· power supply to the rectifiers <strong>of</strong> the respective battery from side source;<br />

· in blackout mode when the batteries are not powered, battery load reduction by<br />

excluding duplicating loads or limiting the loads.<br />

1.4 MAIN DATA FOR SFS<br />

1.4.1 Main data <strong>of</strong> spent fuel storage<br />

The storage facility is an independent building <strong>of</strong> the <strong>NPP</strong> site containing a pool with four<br />

sections <strong>for</strong> storage and respective handling equipment required <strong>for</strong> spent nuclear fuel (SNF)<br />

handling [25].<br />

1.4.1.1 Storage facility type. Commissioning date<br />

The initial design <strong>of</strong> SFS provides <strong>for</strong> its use <strong>for</strong> the time <strong>of</strong> storage <strong>of</strong> SNF from reactors<br />

VVER-440 be<strong>for</strong>e its transfer to Russia. Be<strong>for</strong>e completion <strong>of</strong> construction <strong>of</strong> the facility design has<br />

been prepared <strong>for</strong> additional equipment <strong>of</strong> SFS <strong>for</strong> intake and temporary storage <strong>of</strong> SNF from<br />

VVER-1000 reactors. Construction <strong>of</strong> SFS on <strong>Kozloduy</strong> <strong>NPP</strong> site has been completed in late 1990<br />

and be<strong>for</strong>e obtaining Authorization <strong>for</strong> operation in 2001 it was operated with temporary permit.<br />

The storage facility is wet type, which implies SNF storage in baskets in a pool under water.<br />

1.4.1.2 SFS design features<br />

SFS building is a rein<strong>for</strong>ced concrete structure, partly solid and partly prefabricated, and<br />

supporting structures are metal.<br />

The design capacity <strong>of</strong> the SFS is as follows:<br />

· maximum number <strong>of</strong> baskets - 168;<br />

· maximum total capacity <strong>of</strong> the energy output shall not exceed 1064 kW;<br />

· maximum energy output capacity in one compartment shall not exceed 555 kW.<br />

1.4.1.3 Systems and Equipment <strong>for</strong> Storage and Transportation <strong>of</strong> SNF<br />

The SNF storage and transportation system is a compilation <strong>of</strong> facilities and equipment<br />

designed <strong>for</strong> receiving, continuous storage under water <strong>of</strong> assemblies and packages with SNF.<br />

A SNF pool (SFP) is located in the storage facility with four fuel storage compartments.<br />