“<strong>Kozloduy</strong> <strong>NPP</strong>” PLC<br />

SUMMARY REPORT<br />

<strong>for</strong> <strong>Conduct</strong> <strong>of</strong> <strong>Kozloduy</strong> <strong>NPP</strong><br />

<strong>Stress</strong> <strong>Tests</strong><br />

For SFS equipment power supply a substation with two dry trans<strong>for</strong>mers have been<br />

constructed with power <strong>of</strong> 630 kVА and two-section switchgear, with automatic switch to backup<br />

equipment between the sections. The power is supplied to the substation by two independent cable<br />

lines from 6 kV sections on units 3 and 4.<br />

1.4.2.7.1.1 Cable traces and sections<br />

The main elements <strong>for</strong>ming the SFS electric power supply logic are as follows:<br />

· two trans<strong>for</strong>mers 6/0,4 kV ;630 kVА: They are located in one room <strong>of</strong> SFS.<br />

· two 0,4 kV sections (I and II): Each <strong>of</strong> the sections is connected with one <strong>of</strong> the<br />

trans<strong>for</strong>mers.<br />

· 9 assemblies 0,4 kV: four <strong>of</strong> the assemblies are connected with the operating power<br />

supply from SFS I section (operating) and from SFS II section (backup) and are located in<br />

one room <strong>of</strong> the SFS. The other 4 are connected with power supply from SFS section I<br />

(operating) and SFS ІІ section (backup) and are located in a separate room and one separate<br />

assembly with power supply from SFS I section (operating) and from EDGP (backupuninterruptible),<br />

which is located in a separate room.<br />

1.4.2.7.1.2 Logics, layout and protection against internal and external events<br />

The auxiliary electric equipment is located in separate rooms <strong>of</strong> SFS, which are seismically<br />

and fire resistant. To decrease the fire hazard, the greater part <strong>of</strong> the cables is with cover made <strong>of</strong><br />

inflammable material. Besides, treatment <strong>of</strong> cable sheaves with fire protection composition is<br />

provided.<br />

1.4.2.7.2 Backup power supply<br />

The SFS power supply logic is implemented with two independent channels <strong>for</strong> operating<br />

<strong>of</strong>f-site power supply.<br />

1.4.2.7.2.1 Independence, physical separation and protection against external and internal<br />

impacts<br />

The power and control cables routs <strong>of</strong> the two independent channels <strong>of</strong> SFS electric power<br />

supply are specially separated – they go through separate rooms, or where impossible, by different<br />

walls <strong>of</strong> the room.<br />

1.4.2.7.2.2 Restrictions in availability <strong>of</strong> backup power supply sources and external measures<br />

to extend operability time<br />

In case <strong>of</strong> failure to power supply to one <strong>of</strong> the auxiliary switchgear sections due to external<br />

cause (failure to trans<strong>for</strong>mer or in 6 kV chain) automatically switches <strong>of</strong>f the automatic circuit<br />

breaker and entire load on auxiliary trans<strong>for</strong>mer substations set is connect to the single trans<strong>for</strong>mer.<br />

48/202