Technical DataDG FG JG LG MG NG PGUndervoltage TripDrop voltage (percentage) V 35% – 70% 35% – 70% 35% – 70% 35% – 70% 35% – 70% 35% – 70% 35% – 70%Pick-up voltage (percentage) V 70% – 85% 70% – 85% 70% – 85% 70% – 85% 70% – 85% 70% – 85% 70% – 85%Power consumption (continuous) at:110 – 127 V AC VA 1 1 1 1 1.1 1.1 1.1220 – 250 V AC VA 2.1 2.1 2.1 2.1 2.1 2.1 2.1208 V AC VA 1.2 1.2 1.2 1.2 1.2 1.2 1.2277 V AC VA 1.4 1.4 1.4 1.4 1.4 1.4 1.4380 – 415 V AC VA 1.9 1.9 1.9 1.9 1.9 1.9 1.9440 – 480 V AC VA 2.2 2.2 2.2 2.2 2.2 2.2 2.2500 – 525 V AC VA 2.5 2.5 2.5 2.5 2.5 2.5 2.5600 V AC VA 2.8 2.8 2.8 2.8 2.8 2.8 2.8Max. opening time ms 50 50 50 50 50 50 50Motorized Operating MechanismMotor with stored energy mechanism(synchronizable) X X X X X X XMotor Operator X XMax. switching rate (per hour) 120 120 120 60 60 30 30Command duration ms 20 – 50 20 – 50 20 – 50 20 – 50 20 – 50 — —Closing time ms