F-19<br />

E6581381<br />

[Parameter setting]<br />

Title Function Adjustment range Default setting<br />

VIA input point 1 setting 0-100 (%) 0<br />

VIA input point 1 frequency 0.0-200.0 (Hz) 0.0<br />

VIA input point 2 setting 0-100 (%) 100<br />

VIA input point 2 frequency 0.0-200.0 (Hz)<br />

50.0 (WP type)<br />

60.0 (WN type)<br />

VIB input point 1 setting 0-100 (%) 0<br />

VIB input point 1 frequency 0.0-200.0 (Hz) 0.0<br />

VIB input point 2 setting 0-100 (%) 100<br />

VIB input point 2 frequency 0.0-200.0 (Hz)<br />

50.0 (WP type)<br />

60.0 (WN type)<br />

Communication command point 1 setting 0-100 (%) 0<br />

Communication command point 1 frequency 0.0-200.0 (Hz) 0.0<br />

Communication command point 2 setting 0-100 (%) 100<br />

Communication command point 2 frequency 0.0-200.0 (Hz)<br />

50.0 (WP type)<br />

60.0 (WN type)<br />

Note: Don't set the same value between point 1 and point 2. If set the same falue, the is displayed.<br />

1) 0-10Vdc voltage input adjustment (VIA, VIB)<br />

VIA, VIB terminals<br />

/<br />

60 ( Hz )<br />

Output<br />

frequency<br />

/<br />

0 ( Hz)<br />

/<br />

0 (%)<br />

0<br />

Frequency commnd<br />

/<br />

100 (%)<br />

10V voltage signal<br />

・The output frequency with<br />

respect to the voltage input is<br />

adjusted according to the<br />

selected reference point.<br />

・Gradient and bias can be set<br />

easily.<br />

2) 4-20mAdc current input adjustment (VIA: VIA (SW3) slide switch in the I position)<br />

VIA terminal<br />

Output<br />

frequency<br />

<br />

60 ( Hz )<br />

<br />

0 ( Hz)<br />

<br />

20 (%)<br />

4<br />

Frequency commnd<br />

・The output frequency with respect to<br />

the current input is adjusted<br />

according to the selected reference<br />

point.<br />

・Gradient and bias can be set easily.<br />

・Set to to create a current<br />

input from 0 to 20mA.<br />

<br />

100 (%)<br />

20mA current signal<br />

6

Hooray! Your file is uploaded and ready to be published.

Saved successfully!