6<br />

6.17.4 Emergency stop<br />

: Emergency stop<br />

: Emergency DC braking time<br />

F-60<br />

E6581381<br />

• Function<br />

These parameters allow you to specify how to stop operation using an external control device when<br />

an external trip occurs. When operation is stopped, the trip and the FL relay also are activated.<br />

When setting to (emergency DC braking), set also (DC braking rate) and<br />

(emergency braking time)<br />

1) External trip stop via terminals<br />

The external trip stop function can be executed via the a-contact. Proceed as follows to assign an<br />

external stopping terminal and select the stopping method:<br />

[Parameter setting]<br />

Title Function Adjustment range<br />

0: Coast stop<br />

Default setting<br />

Emergency stop selection<br />

1: Slowdown stop<br />

2: Emergency DC braking<br />

0<br />

Emergency DC braking time 0.0 ~ 20.0 [sec] 1.0<br />

DC braking current 0-100 (%) 50<br />

(Example of terminal assignment): Assigning the trip stop function to the RES terminal<br />

Title Function Adjustment range Setting value<br />

11 (External trip<br />

Input terminal selection 3 (RES) 0-72<br />

stop)<br />

Note 1: Emergency stopping via the specified terminal is possible, even during panel operation.<br />

Note 2: If DC braking is not needed to bring the motor to a stop under normal conditions, although is<br />

set to 2 (emergency DC braking), set the DC braking starting frequency () at 0.0 Hz.<br />

2) Emergency stopping from the operation panel<br />

Emergency stopping from the operation panel is possible<br />

by pressing the STOP key on the panel twice while the inverter is not in the panel control mode.<br />

(1) Press the STOP key ............................... "" will blink.<br />

(2) Press the STOP<br />

key once again Operation will come to a trip stop in accordance with the setting<br />

of the parameter.<br />

After this, "" will be displayed and a failure detection signal<br />

generated (FL relay deactivated).