6<br />
6.17.4 Emergency stop<br />
: Emergency stop<br />
: Emergency DC braking time<br />
F-60<br />
E6581381<br />
• Function<br />
These parameters allow you to specify how to stop operation using an external control device when<br />
an external trip occurs. When operation is stopped, the trip and the FL relay also are activated.<br />
When setting to (emergency DC braking), set also (DC braking rate) and<br />
(emergency braking time)<br />
1) External trip stop via terminals<br />
The external trip stop function can be executed via the a-contact. Proceed as follows to assign an<br />
external stopping terminal and select the stopping method:<br />
[Parameter setting]<br />
Title Function Adjustment range<br />
0: Coast stop<br />
Default setting<br />
Emergency stop selection<br />
1: Slowdown stop<br />
2: Emergency DC braking<br />
0<br />
Emergency DC braking time 0.0 ~ 20.0 [sec] 1.0<br />
DC braking current 0-100 (%) 50<br />
(Example of terminal assignment): Assigning the trip stop function to the RES terminal<br />
Title Function Adjustment range Setting value<br />
11 (External trip<br />
Input terminal selection 3 (RES) 0-72<br />
stop)<br />
Note 1: Emergency stopping via the specified terminal is possible, even during panel operation.<br />
Note 2: If DC braking is not needed to bring the motor to a stop under normal conditions, although is<br />
set to 2 (emergency DC braking), set the DC braking starting frequency () at 0.0 Hz.<br />
2) Emergency stopping from the operation panel<br />
Emergency stopping from the operation panel is possible<br />
by pressing the STOP key on the panel twice while the inverter is not in the panel control mode.<br />
(1) Press the STOP key ............................... "" will blink.<br />
(2) Press the STOP<br />
key once again Operation will come to a trip stop in accordance with the setting<br />
of the parameter.<br />
After this, "" will be displayed and a failure detection signal<br />
generated (FL relay deactivated).