6.17.6 Input phase failure detection<br />

: Input phase failure detection mode selection<br />

F-62<br />

E6581381<br />

• Function<br />

This parameter detects inverter input Phase failure. If the abnormal voltage status of main circuit<br />

capacitor persists for few minutes or more, the tripping function and the FL relay will be activated.<br />

Therefore, input phase failures cannot always be detected. A trip information will be<br />

displayed.<br />

If the power capacity is larger than the inverter capacity (more than 200kVA or more than 10 times),<br />

detection errors may occur. If this actually happens, install an input AC reactor.<br />

=: No tripping (Failure signal FL not activated)<br />

=: Phase failure detection is enabled during operation. The inverter will trip if the abnormal voltage<br />

status of main circuit capacitor persists for ten minutes or more. (Failure signal FL activated)<br />

Title Function Adjustment range Default setting<br />

<br />

Input phase failure detection mode<br />

selection<br />

0: Disabled, 1: Enabled 1<br />

Note: Setting to (input phase failure detection: disabled) may result in a breakage of the<br />

capacitor in the inverter main circuit if operation is continued under a heavy load in spite of the<br />

occurrence of an input phase failure.<br />

6.17.7 Control mode for small current<br />

: Small current detection current hysteresis<br />

: Small current trip/alarm selection<br />

: Small current detection current<br />

: Small current detection time<br />

• Function<br />

The parameter allows the inverter to be tripped if a current smaller than the specified<br />

value flows for more than the -specified time. When tripping is selected, enter the<br />

detection time to tripping. Trip information is displayed as "".<br />

=: No tripping (Failure signal FL not activated).<br />

A small current alarm can be put out by setting the output terminal function selection parameter.<br />

=: The inverter will trip (Failure signal FL activated) if a current below the current set with <br />

flows for the period of time specified with .