VF-FS1 Industrial Inverter - Toshiba
VF-FS1 Industrial Inverter - Toshiba
VF-FS1 Industrial Inverter - Toshiba
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
Voltage<br />
class<br />
Three-phase<br />
200V class<br />
Three-phase<br />
400V class<br />
AIC, Fuse and Wire sizes<br />
Capacity<br />
of<br />
applicable<br />
motor<br />
(kW)<br />
<strong>Inverter</strong> model<br />
AIC (A)<br />
(Interrupting<br />
capacity)<br />
I-7<br />
Fuse class<br />
and<br />
current (A)<br />
Maximum<br />
input<br />
voltage<br />
(V)<br />
Input wire<br />
sizes of<br />
power circuit<br />
Out put<br />
wire sizes<br />
of power<br />
circuit<br />
E6581381<br />
Earth<br />
0.4 <strong>VF</strong><strong>FS1</strong>-2004PM AIC 5000A J 3A max. 240 AWG 14 AWG 14 AWG 14<br />
0.75 <strong>VF</strong><strong>FS1</strong>-2007PM AIC 5000A J 6A max. 240 AWG 14 AWG 14 AWG 14<br />
1.5 <strong>VF</strong><strong>FS1</strong>-2015PM AIC 5000A J 10A max. 240 AWG 14 AWG 14 AWG 14<br />
2.2 <strong>VF</strong><strong>FS1</strong>-2022PM AIC 5000A J 15A max. 240 AWG 14 AWG 14 AWG 14<br />
4.0 <strong>VF</strong><strong>FS1</strong>-2037PM AIC 5000A J 25A max. 240 AWG 12 AWG 10 AWG 12<br />
5.5 <strong>VF</strong><strong>FS1</strong>-2055PM AIC 22000A J 35A max. 240 AWG 10 AWG 8 AWG 10<br />
7.5 <strong>VF</strong><strong>FS1</strong>-2075PM AIC 22000A J 45A max. 240 AWG 8 AWG 8 AWG 10<br />
11 <strong>VF</strong><strong>FS1</strong>-2110PM AIC 22000A J 70A max. 240 AWG 6 AWG 6 AWG 10<br />
15 <strong>VF</strong><strong>FS1</strong>-2150PM AIC 22000A J 90A max. 240 AWG 4 AWG 4 AWG 10<br />
18.5 <strong>VF</strong><strong>FS1</strong>-2185PM AIC 22000A J 100 A max. 240 AWG 4 AWG 3 AWG 8<br />
22 <strong>VF</strong><strong>FS1</strong>-2220PM AIC 22000A J 125A max. 240 AWG 2 AWG 2 AWG 8<br />
30 <strong>VF</strong><strong>FS1</strong>-2300PM AIC 22000A J 175A max. 240 AWG 1/0 AWG 1/0 AWG 6<br />
0.4 <strong>VF</strong><strong>FS1</strong>-4004PL AIC 5000A J 3A max. 480 AWG 14 AWG 14 AWG 14<br />
0.75 <strong>VF</strong><strong>FS1</strong>-4007PL AIC 5000A J 3A max. 480 AWG 14 AWG 14 AWG 14<br />
1.5 <strong>VF</strong><strong>FS1</strong>-4015PL AIC 5000A J 6A max. 480 AWG 14 AWG 14 AWG 14<br />
2.2 <strong>VF</strong><strong>FS1</strong>-4022PL AIC 5000A J 10A max. 480 AWG 14 AWG 14 AWG 14<br />
4.0 <strong>VF</strong><strong>FS1</strong>-4037PL AIC 5000A J 15A max. 480 AWG 14 AWG 14 AWG 14<br />
5.5 <strong>VF</strong><strong>FS1</strong>-4055PL AIC 22000A J 20A max. 480 AWG 14 AWG 14 AWG 14<br />
7.5 <strong>VF</strong><strong>FS1</strong>-4075PL AIC 22000A J 25A max. 480 AWG 12 AWG 12 AWG 14<br />
11 <strong>VF</strong><strong>FS1</strong>-4110PL AIC 22000A J 35A max. 480 AWG 10 AWG 10 AWG 10<br />
15 <strong>VF</strong><strong>FS1</strong>-4150PL AIC 22000A J 45A max. 480 AWG 8 AWG 8 AWG 10<br />
18.5 <strong>VF</strong><strong>FS1</strong>-4185PL AIC 22000A J 60A max. 480 AWG 8 AWG 8 AWG 10<br />
22 <strong>VF</strong><strong>FS1</strong>-4220PL AIC 22000A J 70A max. 480 AWG 6 AWG 6 AWG 10<br />
30 <strong>VF</strong><strong>FS1</strong>-4300PL AIC 22000A J 90A max. 480 AWG 4 AWG 4 AWG 10<br />
37 <strong>VF</strong><strong>FS1</strong>-4370PL AIC 22000A J 110A max. 480 AWG 3 AWG 3 AWG 8<br />
45 <strong>VF</strong><strong>FS1</strong>-4450PL AIC 22000A J 125A max. 480 AWG 2 AWG 1 AWG 8<br />
55 <strong>VF</strong><strong>FS1</strong>-4550PL AIC 22000A J 175A max. 480 AWG 1 AWG 1/0 AWG 6<br />
75 <strong>VF</strong><strong>FS1</strong>-4750PL AIC 22000A J 225A max. 480 AWG 3/0 AWG 3/0 AWG 6<br />
9.2.4 Motor thermal protection<br />
Selects the electronic thermal protection characteristics that fit with the ratings and characteristics of the motor. In<br />
case of multi motor operation with one inverter, thermal relay should be connected to each motor.<br />
9