Calorific values of the inverter and the required ventilation<br />
A-22<br />
E6581381<br />
About 5% of the rated power of the inverter will be lost as a result of conversion from AC to DC or from DC to<br />
AC. In order to suppress the rise in temperature inside the cabinet when this loss becomes heat loss, the<br />
interior of the cabinet must be ventilated and cooled.<br />
The amount of forcible air-cooling ventilation required and the necessary heat discharge surface quantity<br />
when operating in a sealed cabinet according to motor capacity are as follows.<br />
Note1: The heat loss for the optional external devices (input reactor, radio noise reduction filters, etc.) is not<br />
included in the calorific values in the table<br />
Note2: Case of 100% Load Continuation operation.<br />
Voltage class<br />
Three-Phase<br />
200V class<br />
Three-Phase<br />
400V class<br />
Operating motor<br />
capacity<br />
(kW)<br />
Calorific Values (w)<br />
Carrier frequency<br />
8kHz<br />
Carrier frequency<br />
12kHz<br />
Amount of forcible air<br />
cooling ventilation required<br />
(m 3 /min)<br />
Heat discharge surface<br />
area required for sealed<br />
storage cabinet(m 2 )<br />
0.4 - 44 0.25 0.88<br />
0.75 - 63 0.36 1.26<br />
1.5 - 101 0.58 2.02<br />
2.2 - 120 0.68 2.4<br />
4.0 - 193 1.1 3.86<br />
5.5 - 249 1.42 4.98<br />
7.5 - 346 1.97 6.92<br />
11 - 459 2.62 9.18<br />
15 - 629 3.59 12.58<br />
18.5 698 - 3.98 13.96<br />
22 763 - 4.35 15.26<br />
30 1085 - 6.18 21.7<br />
0.4 - 45 0.26 0.9<br />
0.75 - 55 0.31 1.1<br />
1.5 - 78 0.44 1.56<br />
2.2 - 103 0.59 2.06<br />
4.0 - 176 1.0 3.52<br />
5.5 - 215 1.23 4.3<br />
7.5 - 291 1.66 5.82<br />
11 - 430 2.45 8.6<br />
15 - 625 3.56 12.5<br />
18.5 603 - 3.44 12.06<br />
22 626 - 3.57 12.52<br />
30 847 - 4.83 16.94<br />
37 980 - 5.59 19.60<br />
45 1257 - 7.17 25.14<br />
55 1459 - 8.32 29.18<br />
75 1949 - 11.11 38.98<br />
Panel designing taking into consideration the effects of noise<br />
The inverter generates high frequency noise. When designing the control panel setup, consideration must be<br />
given to that noise. Examples of measures are given below.<br />
• Wire so that the main circuit wires and the control circuit wires are separated. Do not place them in the<br />
same conduit, do not run them parallel, and do not bundle them.<br />
• Provide shielding and twisted wire for control circuit wiring.