13. Before making a service call<br />
- Trip information and remedies<br />
13.1 Trip causes/warnings and remedies<br />
M-1<br />
E6581381<br />
When a problem arises, diagnose it in accordance with the following table.<br />
If it is found that replacement of parts is required or the problem cannot be solved by any remedy described in the<br />
table, contact your <strong>Toshiba</strong> dealer.<br />
[Trip information]<br />
Error code Failure code Problem Possible causes Remedies<br />
0001 Overcurrent during • The acceleration time is too short. • Increase the acceleration time .<br />
0025 acceleration<br />
Overcurrent flowing<br />
in element during<br />
acceleration<br />
• The V/F setting is improper.<br />
• Check the V/F parameter.<br />
• A restart signal is imput to the rotating motor • Use (auto-restart) and <br />
after a momentary stop, etc.<br />
(coast stop).<br />
• A special motor (e.g. motor with a small • Adjust the carrier frequency .<br />
impedance) is used.<br />
• Set the carrier frequency control mode<br />
• There is possibility of Ground fault trip. selection parameter to 1 or 3<br />
(carrier frequency decreased automatically).<br />
0002 Overcurrent during • The deceleration time is too short. • Increase the deceleration time .<br />
0026 deceleration<br />
Overcurrent flowing<br />
in element during<br />
decelearion<br />
• There is possibility of Ground fault trip. • Set the carrier frequency control mode<br />
selection parameter to 1 or 3<br />
(carrier frequency decreased automatically).<br />
0003 Overcurrent during • The load fluctuates abruptly.<br />
• Reduce the load fluctuation.<br />
0027 constant speed<br />
operation<br />
Overcurrent flowing<br />
in element during<br />
operation<br />
• The load is in an abnormal condition.<br />
• There is possibility of Ground fault trip.<br />
• Check the load (operated machine).<br />
• Set the carrier frequency control mode<br />
selection parameter to 1 or 3<br />
(carrier frequency decreased automatically).<br />
<br />
<br />
<br />
0025<br />
0026<br />
0027<br />
Ground fault trip<br />
Arm overcurrent at<br />
start-up<br />
Overheat<br />
• A current leaked from an output cable or the • Check cables, connectors, and so on for<br />
motor to ground.<br />
ground faults.<br />
• A main circuit elements is defective. • Make a service call.<br />
• See “OH” trip information in the next page. • See “OH” trip information in the next page.<br />
(for 200V: 11 to 18.5kW, 400V: 15 to 18.5kW (for 200V: 11 to 18.5kW, 400V: 15 to 18.5kW<br />
models only)<br />
models only)<br />
0004 Overcurrent (An • The insulation of the output main circuit or • Check the cables and wires for defective<br />
overcurrent on the motor is defective.<br />
insulation.<br />
load side at startup)<br />
• The motor has too small impedance.<br />
• 200V: 11 to 18.5kW, 400V: 15 to 18.5kW<br />
• When using 200V: 11 to 18.5kW, 400V: 15<br />
to 18.5kW model, check cables, connectors,<br />
model was started, although a current is<br />
leaked from an output cable or the motor to<br />
ground.<br />
and so on for ground faults.<br />
0005 Arm overcurrent at • A main circuit elements is defective. • Make a service call.<br />
*<br />
<br />
0008<br />
start-up<br />
Input phase failure<br />
• There is possibility of Ground fault trip.<br />
• A phase failure occured in the input line of<br />
the main circuit.<br />
• Check the main circuit input line for phase<br />
failure.<br />
• Enable (input phase failure<br />
detection).<br />
• Check the capacitor in the main circuit for<br />
exhaustion.<br />
13<br />
• The input voltage fluctuates abnormally. • Make a service call.<br />
*<br />
<br />
0009 Output phase<br />
failure<br />
• A phase failure occurred in the output line of • Check the main circuit output line, motor,<br />
the main circuit.<br />
etc. for phase failure.<br />
• Enable (Output phase failure<br />
detection).<br />
* You can select a trip ON/OFF by parameters. (Continued overleaf)