5<br />

: Command mode selection<br />

: Frequency setting mode selection 1<br />

E-8<br />

E6581381<br />

• Function<br />

Remote mode selection, these parameters are used to specify which input device (operation panel,<br />

terminal board, RS485 communication) takes priority in entering an operation stop command or a<br />

frequency setting command, VIA, VIB, operation panel, RS485 communication device, external contact<br />

up/down).<br />

At Local mode selection, the start/stop operation and frequency setting by operation panel is prior with no<br />

relation of /setting.<br />

<br />

Title Function Adjustment range Default setting<br />

Command mode selection<br />

Programmed value<br />

Terminal board<br />

: operation<br />

:<br />

Operation panel<br />

operation<br />

0: Terminal board<br />

1: Operation panel<br />

2: RS485 communication<br />

ON and OFF of an external signal Runs and stops operation.<br />

Press the RUN<br />

and STOP keys on the operation panel to start and stop.<br />

Serial communication<br />

Run and stop through serial communication.<br />

operation<br />

* There are two types of function: the function that conforms to commands selected by , and the function<br />

that conforms only to commands from the terminal board.<br />

⇒ See the table of input terminal function selection in Chapter 11.<br />

* When priority is given to commands from a linked computer or terminal board, they have priority over the<br />

setting of .<br />