Output frequency [Hz]<br />

+ <br />

<br />

― <br />

Over set frequency attainment signal<br />

RY-RC<br />

FLA-FLC-FLB<br />

Over set frequency attainment<br />

signal: Inverted<br />

6.2 Input signal selection<br />

6.2.1 Changing the functions of VIA terminal<br />

: VIA terminal function selection<br />

o<br />

F-5<br />

Time [s]<br />

ON<br />

OFF<br />

ON<br />

OFF<br />

E6581381<br />

• Function<br />

This parameter allows you to choose between signal input and contact signal input for the VIA terminal.<br />

[Parameter setting]<br />

Title Function Adjustment range<br />

0: VIA - analog input<br />

Default setting<br />

<br />

Analog/contact input<br />

function selection (VIA<br />

terminal)<br />

1: VIA - contact input (Sink)<br />

2: VIA - contact input (Source)<br />

* When using the VIA terminal as contact input terminals in sink logic connection, be sure to insert a<br />

resistor between the P24 terminal and the VIA terminal. (Recommended resistance: 4.7kΩ-1/2W)<br />

Note: When using the VIA terminal as a contact input terminal, be sure to turn the VIA (SW3) slide switch to<br />

the V position.<br />

The figure on the right shows an example of the<br />

connection of input terminal VIA when it is used as<br />

contact input terminal. This example illustrates the<br />

connection when the inverter is used in sink<br />

(Negative) logic mode.<br />

In case source (Positive) logic mode, connect the<br />

resistor between VIA and CC.<br />