Prohibited<br />

5<br />

E6581381<br />

Caution See item<br />

• Observe all permissible operating ranges of motors and mechanical equipment. (Refer to<br />

the motor's instruction manual.)<br />

Not observing these ranges may result in injury.<br />

When sequence for restart after a momentary failure is selected (inverter)<br />

Mandatory<br />

Caution See item<br />

• Stand clear of motors and mechanical equipment.<br />

If the motor stops due to a momentary power failure, the equipment will start suddenly<br />

after power recovers. This could result in unexpected injury.<br />

• Attach warnings about sudden restart after a momentary power failure on inverters,<br />

motors and equipment for prevention of accidents in advance.<br />

When retry function is selected (inverter)<br />

Mandatory<br />

3.<br />

6.12.1<br />

6.12.1<br />

Caution See item<br />

• Stand clear of motors and equipment.<br />

If the motor and equipment stop when the alarm is given, selection of the retry function will<br />

restart them suddenly after the specified time has elapsed. This could result in unexpected<br />

injury.<br />

• Attach warnings about sudden restart in retry function on inverters, motors and equipment<br />

for prevention of accidents in advance.<br />

Maintenance and inspection<br />

Prohibited<br />

Mandatory<br />

Warning<br />

• Do not replace parts.<br />

This could be a cause of electric shock, fire and bodily injury. To replace parts, call the<br />

local sales agency.<br />

• The equipment must be inspected every day.<br />

If the equipment is not inspected and maintained, errors and malfunctions may not be<br />

discovered and that could result in accidents.<br />

• Before inspection, perform the following steps.<br />

(1) Turn off all input power to the inverter.<br />

(2) Wait at least ten minutes and check to make sure that the charge lamp is no longer lit.<br />

(3) Use a tester that can measure DC voltages (800VDC or more), and check to make<br />

sure that the voltage to the DC main circuits (across PA/+ and PC/-) is 45V or less.<br />

If inspection is performed without performing these steps first, it could lead to electric<br />

shock.<br />

6.12.3<br />

6.12.3<br />

See item<br />

14.2<br />

14.<br />

14.<br />