6.17.13 Trip at VIA low level input mode<br />
: Trip at VIA low level input mode<br />
: Action in the event of VI/II analogue input wire breakage<br />
: Fallback speed<br />
• Function<br />
The inverter will trip or alarm if the VIA value remains below the specified value for about 0.3<br />
seconds. In such a case, trip:"" , alarm "" is displayed.<br />
F-68<br />
E6581381<br />
=0: Disabled ........The detection function is disabled.<br />
=1-100 ................The inverter will trip if the VIA value remains below the specified value for about<br />
0.3 seconds.<br />
Title Function Adjustment range Default setting<br />
<br />
Trip at VIA low level input<br />
mode<br />
0: Disabled<br />
1-100%<br />
0<br />
f644 Action in the event of VI/II 0: Coast stop (Trip mode e-18)<br />
0<br />
analogue input wire 1: Coast stop (Alarm mode alos)<br />
breakage<br />
2: Fallback speed (Alarm mode alos)<br />
3: Speed maintain (Alarm mode alos)<br />
4: Slowdown stop (Alarm mode alos)<br />
f649 Fallback speed 0.0-fh 0.0<br />
Note : The VIA input value may be judged earlier to be abnormal, depending on the degree of deviation of<br />
the analog data detected.<br />
6.17.14 Parts replacement alarms<br />
: Annual average ambient temperature (For parts replacement alarms)<br />
• Function<br />
You can set the inverter so that it will calculate the remaining useful lives of the cooling fan, main<br />
circuit capacitor and on-board capacitor from the ON time of the inverter, the operating time of the<br />
motor, the output current (load factor) and the setting of , and that it will display and send out<br />
an alarm through output terminals when each component is approaching the time of replacement.<br />
Title Function Adjustment range Default setting<br />
<br />
Annual average ambient temperature<br />
(For parts replacement alarms)<br />
1: -10 to +10°C<br />
2: 11 to 20°C<br />
3: 21 to 30°C<br />
4: 31 to 40°C<br />
5: 41 to 50°C<br />
6: 51 to 60°C<br />
Display of part replacement alarm information<br />
Part replacement alarm information (⇒ See page H-3) in the Status monitor mode allows you to check<br />
on the time of replacement.<br />
An example of display: <br />
3