3.1.1 How to start and stop<br />

Example of a setting procedure<br />

Key operated LED display Operation<br />

MODE<br />

ENT<br />

ENT<br />

<br />

Displays the operation frequency (operation stopped).<br />

(When standard monitor display selection = [Operation<br />

frequency])<br />

Displays the first basic parameter [Wizard function ()].<br />

Press either the or key to select “”.<br />

Press ENT key to display the parameter setting. (Default setting:).<br />

Change the parameter to (panel) by pressing the key.<br />

⇔<br />

Press the ENT key to save the changed parameter. and the<br />

parameter set value are displayed alternately.<br />

(1) Start and stop using the operation panel keys (=)<br />

Use the RUN and STOP keys on the operation panel to start and stop the motor.<br />

RUN : Motor starts. STOP<br />

: Motor stops.<br />

To switch between forward run and reverse run from the control panel, the parameter <br />

(forward/reverse run selection) needs to be set to or .<br />

C-3<br />

E6581381<br />

(2) RUN/STOP by means of an external signal to the terminal board (=):<br />

Sink (Negative) logic<br />

Use external signals to the inverter terminal board to start and stop the motor.<br />

Short F and CC terminals: run forward<br />

Open F and CC terminals: slow down and stop<br />

(3) Coast stop<br />

The standard default setting is for slowdown stop. To<br />

make a coast stop, assign a "1(ST)" terminal function<br />

to an idle terminal using the programmable terminal<br />

function.<br />

Change to =.<br />

For coast stop, open the ST-CC when stopping the<br />

motor in the state described at left.The monitor on the<br />

inverter at this time will display .<br />

Frequency<br />

Motor<br />

speed<br />

F-CC<br />

ST-CC<br />

F-CC<br />

Coast stop<br />

Slow down<br />

and stop<br />

ON<br />

OFF<br />

ON<br />

OFF<br />

ON<br />

OFF<br />