Coast stop (=)<br />

E-5<br />

E6581381<br />

Setting for coast stopping. In sink logic mode, closing the circuit between the R and CC terminals places the<br />

inverter in standby mode and opening the circuit places it in coast stop mode, because ST (standby signal)<br />

is assigned to the R terminal.<br />

⇒ See section 3.1.1 (3) and 6.3.1 for details.<br />

3-wire operation (=)<br />

Can be operated by a momentary push-button. HD (operation holding) is assigned to the terminal R. A selfholding<br />

of operations is made in the inverter by connecting the stop switch (b-contact) to the R terminal and<br />

connecting the running switch (a-contact) to the F terminal.<br />

Three-wire operation (one-touch operation)<br />

You can carry out operation by simply pressing the ON/OFF button.<br />

Standard connection diagram- Forward run<br />

F<br />

R (HD)<br />

RES<br />

CC<br />

PLC<br />

PP<br />

VIA<br />

VIB<br />

CC<br />

RUN<br />

STOP<br />

Selecting HD (operation holding) with the input<br />

terminal selection parameter<br />

Select HD (operation holding) using the input<br />

terminal selection parameter, and turn HD on to<br />

get the inverter ready for operation or turn HD<br />

off to stop operation.<br />

Parameter setting:<br />

When parameter is set to , the following<br />

parameters are set automatically.<br />

: (ST)<br />

: (terminal board).<br />

R terminal : (operation holding).<br />

Note 1 : Even if each terminal is ON, any command entered<br />

through a terminal is ignored when power is turned<br />

on (to prevent the load from starting to move<br />

unexpectedly). Enable to turn the input terminal on<br />

at power on.<br />

Note 2 : When HD is OFF, any attempt to turn on F is<br />

ignored.<br />

Note 3 : Sending out a RUN signal during DC braking has<br />

no effect in stopping DC braking.<br />