Table 3-2 MRS Interlocks<br />

2 Shut down Inclined Conveyor and<br />

Retrieval Bin Discharge Feeder if<br />

Transfer Conveyor is not running.<br />

3<br />

4<br />

13<br />

19<br />

~~ ~ ~~~<br />

IShut down Transfer Conveyor if Feed<br />

'Conveyor is not running.<br />

i shut down Inclined Conveyor (both<br />

motors) on High-High Current or Low<br />

Speed.<br />

33 Shut down Retrieval Bin Discharge<br />

Feeder if Inclined Conveyor shuts<br />

- - - - __ - - __ - - - do!?!, . - - - -- - - - - -. - - - - - -- -<br />

39<br />

Allow feeder to run only if one <strong>of</strong> the<br />

two discharge valves is open.<br />

Allow Retrieval Bin Discharge Feeder<br />

to run only if discharge valve is open.<br />

Shut down Retrieval Bin Discharge<br />

Feeder on High-High Current or Low<br />

Speed.<br />

. Table 3-3 MRS Setpoints<br />

Process Control Plan for the Silo 3 Project<br />

Document No. 40430-PL-0003. Rev. 1<br />

Jacobs Project Number 35H19605<br />

September 5, 2003<br />

5069<br />

~ FDR-11-5100 ZS-AOV-25-5260A<br />

, ZS-AOV-2 5-5 260B<br />

FDR-11-5100 YS-FDR-10-5 102<br />

DFC-11-5056 II-DFC-11-5056<br />

SSL-DFC-11-5056<br />

FDR-11-5106 YS-AOV-11-5009<br />

FDR-11-5106 1 II-DFC-11-5056<br />

14 amps High-High Current (1 3)<br />

DFC-11-5056 SSL-DFC-11-5056 0 rprn Low speed (1 3)<br />

FDR-11-5 100 II-FDR-11-5 1 00 Current:<br />

2.5 amps Low Operator Action<br />

4.5 amps High Operator Action<br />

4.8 amps High-High Operator Action<br />

FDR-11-5100 SSL-FDR-11-5100 0 rpm Low speed (2)<br />

FDR-11-5 106 II-FDR-11-5 106 Current:.<br />

6amps Low Operator Action<br />

12 amps High Operator Action<br />

14 amps High-High (39)<br />

FDR-11-5106 SSL-FDR-11-5106 0 RPM Low Speed (39)<br />

All setpoints will be reviewed and modified as necessary during startup.<br />