Process Description for the Silo 3 Project<br />

Document No. 40430-RP-0003, Rev. 1<br />

Jacobs Project No. 35H19605<br />

September 5, 2003<br />

* 2, ,** '-<br />

tempecat9re; ,pH, etc.; and keeps any solids in suspension. The tank's bottom outlet is<br />

piped to the suction side <strong>of</strong> the Wastewater Pump, which is a low-head centrifugal pump<br />

with acid-resistant wetted parts. Wastewater Tank influents are as follows:<br />

0 Excavator Room Sump and Excavator Service Room Sump: These rooms' floors are<br />

sloped to drain into concrete sumps. Infrequently, water may enter the sumps as a<br />

result <strong>of</strong> washdown and/or excessive misting. Air-operated diaphragm sump pumps are<br />

provided in each sump to transfer water to the Wastewater Tank.<br />

0<br />

0<br />

Wastewater Tank Area Sump: This concrete sump picks up leakage and spillage from<br />

the curbed area surrounding the Wastewater Tank, the Additive Mix Tank, and the two<br />

Additive Charge Tanks. In the Packaging Area, floor drains are provided to transfer<br />

wastewater to the Wastewater Tank Area Sump. An air-operated diaphragm sump<br />

pump transfers the sump's contents into the Wastewater Tank.<br />

In addition to the three sumps, the Wastewater Tank can also receive water from the<br />

process water line for dilution and flushing (see Section 6.4).<br />

Once the level in the Wastewater Tank reaches a preset high value, input from all sources<br />

is shut <strong>of</strong>f. The tank's contents are then sampled and analyzed to ensure that they meet<br />

the Advanced Wastewater Treatment (AWWT) facility waste acceptance criteria.<br />

Arrangements are then made with AWWT personnel to transfer the tank's contents to the<br />

AWWT facility. This is accomplished by using the Wastewater Pump to transfer<br />

wastewater to a tanker truck.<br />