H0026-2<br />

ACU-70-5702<br />

DPW-70-6016<br />

DBR-70-6020<br />

DPR-70-6022<br />

Table 10-2C Miscellaneous HVAC Svsterns Interlocks<br />

is opened; start up exhaust fan when<br />

Door 0058 is closed.<br />

temperature rises above 6OoF.<br />

Table 10-3A Supply Air System Setpoints<br />

Process Control Plan for the Silo 3 Project<br />

Document No. 40430-PL-0003, Rev. 1<br />

Jacobs Project Number 35H 19605<br />

September 5, 2003<br />

FAP-92-5860<br />

I ACU-70-5701 I TI-ACU-70-5701 I 8 5 O F I High Temperature I Operator Action I I<br />

TI-ACU-70-5702 6OoF High Temperature (H0027-3)<br />

PDIC-DPR-70-6016<br />

-0.4 in. wg<br />

-o.25 in. wg<br />

Low Diff Pressure<br />

High Diff, Pressure<br />

Operator Action<br />

Operator Action<br />

PDIC-DPR-70-6020<br />

-0.3 in. wg<br />

-o.2 in. wg<br />

Low Diff Pressure<br />

High Diff. Pressure<br />

(H0022-1)<br />

(H0022-1)<br />

PDIC-DPR-70-6022<br />

-0.3 in. wg<br />

-o.2 in. wa<br />

Low Diff Pressure<br />

Hioh Diif. Pressure<br />

(H0022-2)<br />

27 Unlike the P&IDs, The HVAC Control Diagrams do not assign a unique number to each interlock.<br />

Accordingly, this table uses both the interlock number and the sheet number for uniqueness.<br />

28 All setpoints will be reviewed and modified as necessary during startup.<br />

10-8<br />

000144<br />