- m.’!aBsL-<br />

__<br />

- 5-0-69 - ~<br />

Process Control Plan for the Silo 3 Project<br />

Document No. 40430-PL-0003, Rev. 1<br />

. Jacobs Project Number 35H19605<br />

September 6, 2003.<br />

___<br />

‘e<br />

4.0 PROCESS VENT SYSTEM (SYSTEM 19)<br />

The following PFD and P&IDs illustrate the Process Vent System (PVS):<br />

94X-3900-F-0143 1 F0003 Process Vent and Packaging Systems<br />

94X-3900-N-01439 NO106 Process Vent System, Sheet 1 <strong>of</strong> 2<br />

94X-3900-N-01440 NO107 Process Vent System, Sheet 2 <strong>of</strong> 2<br />

The PVS is a collection and filtration system for process vent streams from the Silo 3<br />

Project. These streams are associated with retrieval and packaging <strong>of</strong> Silo 3 material and<br />

are potentially contaminated with radon and particulates. The major process areas being<br />

vented are located on Silo 3 (via the VWEs), the Excavator Room, and the Packaging Area.<br />

Streams collected by the PVS pass through baghouse dust collectors and HEPA/ULPA filter<br />

housings, and are then routed to the Exhaust Stack, where they are sampled and<br />

discharged to the atmosphere.<br />

FQr a description <strong>of</strong> how the PVS interacts with the PRS, MRS, and HVAC systems, see<br />

Section 2.0.<br />

4.1 PVS EQUIPMENT<br />

Major equipment in the W S<br />

0<br />

is as follows:<br />

------------------<br />

DCL-19-5202A&B: Process Vent Dust Collectors A&B<br />

HBN-19-5205A&B: Fines Collection Bins A&B<br />

FLT-19-5204A&B: Process HEPA Filters A&B<br />

FAN-1 9-5206A&B: Process Exhaust Fans A&B<br />

STK-19-5209: Exhaust Stack<br />

0 CEM-19-5208: Continuous Emissions Monitor (CEM) (Radon, Particulate, and Flow<br />

Monitoring)<br />

For ’detailed descriptions <strong>of</strong> all equipment associated with the PVS, see the PD,<br />

Section 4.4.<br />

4.2 PVS INSTRUMENTATION<br />

Table 4-1 summarizes, by function, all <strong>of</strong> the instrumentation in the PVS.<br />

4.3 PVS CONTROL PHILOSOPHY<br />

The PVS is designed to:<br />

Remove radon and particulate-laden air from the various system components and filter<br />

the particulate decay products prior to discharge.<br />

Reduce radon and particulate concentrations in processing areas.<br />

Detect and measure radon and particulate releases to the atmosphere.<br />

Contaminated gases and dust are drawn through the PVS by redundant centrifugal fans<br />

(FAN-1 9-5206A&B). The fans and associated ductwork are designed to maintain<br />

appropriatevacuum levels in Silo 3, the Excavator Room, the Excavator Service Room, and<br />