6.1.2 Supply Air System (System 70)<br />

Process Description for the Silo 3 Project<br />

Document No. 40430-RP-0003, Rev. 1<br />

Jacobs Project No. 35H19605<br />

September 5, 2003<br />

The Supply Air System comprises Packaged Air Conditioning Units 1, 2, and 3 (ACU-70-<br />

5700, -5710, and -5720). These units draw in ambient air, heat or cool the air (as dictated<br />

by ambient conditions), and distribute it to various "clean, " normally occupied roomslareas<br />

at the head end <strong>of</strong> the cascade ventilation system. Only two <strong>of</strong> the ACUs operate at a<br />

time, with the third on standby.<br />

6.1.3 Exhaust Air System (System 71)<br />

Air from "clean" roomdareas is drawn into those roomdareas with a higher potential for<br />

contamination. Exhaust air is directed to HEPA filters and discharged to the Exhaust Stack.<br />

The Exhaust Air System comprises: Building Filtration Exhaust Fans A&B (FAN-71 -5760<br />

A&B); and Building ULPA/HEPA Exhaust Modules A&B (FLT-71-5770 A&B).<br />

The building ventilation/exhaust system collects air streams from all rooms and areas on<br />

the cascade system (see Table 6-1) and routes them through a system <strong>of</strong> galvanized steel I<br />

ductwork to the Building ULPA/HEPA Exhaust Modules A&B (FLT-71-5770 A&B). Each <strong>of</strong><br />

the two exhaust modules includes roughing filters, HEPA filters, ULPA filters, in-place test<br />

sections, transition pieces, and isolation dampers. Housings for the exhaust modules are<br />

s t a in I e ss s t ee I , s id e-a cc e ss , "bag - i n/ ba g- o ut " housings' ' .<br />

Each <strong>of</strong> the two exhaust modules is sized for 100 percent airflow (i.e., approximately<br />

7,200 acfm). Air is pulled through the exhaust modules by one <strong>of</strong> two centrifugal exhaust<br />

fans (FAN-71-5760 A&B). Exhaust air is discharged from the fans to the Exhaust Stack<br />

(see Section 4.4.5).<br />

6.2<br />

PLANT AND INSTRUMENT AIR SYSTEM (SYSTEM 40)<br />

The following PFD and P&IDs illustrate the Plant and Instrument Air System:<br />

94X-3900-F-0 1 432 F0005 Plant, Instrument, and Breathing Air Systems<br />

94X-3900-N-01441 NO1 08 Plant Air System<br />

94X-3900-N-01444 NO 1 1 1 Plant Air System Connections<br />

94X-3900-N-0 1446 NO 1 1 3 Instrument Air System Connections<br />

The Plant and Instrument Air System provides both compressed and instrument-quality air<br />

for various end users such as baghouse and cartridge filter pulse jets, air-operated valves,<br />

and miscellaneous instrumentation.<br />

6.2.1 Plant/lnstrument Air Equipment (SKD-40-5300)<br />

-The-P-lantllastrument A ir ComDressor Skid (SKD-40-5300) is a fully self-contained, structural<br />

steel skid unit. All components are purchased piped and wired, and ready for installation upon<br />

receipt. The skid includes, but is not limited to, the following equipment:<br />

8 ACP-40-5320A&B: Air Compressors A&B<br />

8<br />

ART-40-531 0: Instrument Air Receiver Tank<br />

8 ADR-40-53 1 2A&B: Desiccant Vessels A&B<br />

" The "bag-in/bag-out" feature minimizes the potential <strong>of</strong> releases during filter changes.<br />