• All components shall be made of non-toxic materials <strong>and</strong> must be reasonably resistant to<br />
corrosion under operating conditions.<br />
• Components must be strong enough to be able to withst<strong>and</strong> pressures 150 % of normal<br />
operating conditions.<br />
• Piping must be installed in such a manner that they do not pose a hazard to the users.<br />
• Pipes must comply with the following sizes <strong>and</strong> fl ow rates show in the following table,<br />
unless accompanied by a hydraulic design:<br />
PIPE SIZE 32mm 38mm 50mm 63mm 76mm 100mm 150mm<br />
GPM PRESSURE SIDE 25 60 90 140 220 350 800<br />
GPM PRESSURE SIDE -<br />
COPPER<br />
20 48 72 96 176 280 640<br />
GPM SUCTION SIDE<br />
TOTAL DYNAMIC HEAD<br />
15 35 50 80 140 220 450<br />
The total dynamic head of the reticulation system shall be calculated. In the absence of any calculations<br />
the following table may be used:<br />
DISTANCE FROM THE MAIN DRAIN TO THE PUMP TOTAL DYNAMIC HEAD (TDID)<br />
300 – 7620 mm 55<br />
7620 – 15240 mm 60<br />
15240 – 22860 mm 65<br />
22860 – 30480 mm 70<br />
30480 – 38100 mm 75<br />
38100 - 45720 80<br />
Beyond 45720 mm Calculations are Required<br />
PUMPS AND MOTORS<br />
Pumps <strong>and</strong> motors are to be installed on each water circulation system <strong>and</strong> shall conform to the<br />
following:<br />
• Pumps must be sized to meet but exceed the fl ow rates required for fi ltering against the<br />
total head developed by the complete water circulation system.<br />
• Pumps must be sized to comply with the required turnover rates.<br />
Swimming<br />
• All equipment must be readily <strong>and</strong> easily accessible for inspection, maintenance <strong>and</strong> repair.<br />
When pumps are installed below the waterline, valves must be installed on permanently<br />
connected suction <strong>and</strong> return lines. The valves must be removable when required.<br />
80