DRAINS<br />
Pools shall be equipped with at least two main drains, located in the deepest portion, at least 900<br />
mm apart. The drains have to be constructed in such a way to prevent suction entrapment under all<br />
operating conditions. An anti-vortex or an approved grate that has a minimum diagonal measurement<br />
of 600 mm, has safe openings of at least four times the area of the drain pipe <strong>and</strong> is securely fi xed into<br />
position to ensure that they are not readily removable by bathers, must cover each drain.<br />
Drains have to be spaced at interval of not exceeding 6.0 metres <strong>and</strong> may not be less more than 1.50<br />
metres from each side wall.<br />
In addition to the above, no check valve may be installed between a suction outlet <strong>and</strong> a pump.<br />
FLOW METER<br />
All public swimming pools must be equipped with fl ow metres that measure the rate of backwash<br />
through the fi lter. The fl ow meter shall be installed between the pump <strong>and</strong> the fi lter on a straight section<br />
of pipe in accordance with the manufacturer’s instructions, in a location where it may easily read. The<br />
meter shall measure the fl ow in litres per second <strong>and</strong> shall be accurate to within 5 % under all fl ow<br />
conditions. The fl ow meter shall further have an indicator that is capable of readings of at least 150 %<br />
of the normal fl ow rate.<br />
SIGHT GLASS<br />
Pressure fi lters systems shall have a sight glass fi tted on the waste discharge pipe.<br />
AIR RELIEF VALVES<br />
Pressure type fi lters shall be equipped with a means to release internal pressure. Each pressure fi lter<br />
shall be equipped with an air relief piping system connected at an accessible point near the crown.<br />
Automatic air relief systems may be used instead of manual systems.<br />
The design of a fi lter with an automatic air relief system as its principal means of air release shall<br />
include lids that provide a slow <strong>and</strong> safe release of pressure.<br />
The design of a separation tank used in conjunction with a fi lter tank shall include a manual means of<br />
air release or a lid that provides a slow <strong>and</strong> safe release of pressure as it is opened.<br />
ACCESS TO EQUIPMENT<br />
All of the above equipment (including all fi ltration equipment) has to readily accessible for inspection,<br />
maintenance <strong>and</strong> replacement purposes.<br />
FILTRATION<br />
Swimming<br />
The maximum fi ltration rate shall not exceed the design fl ow rates prescribed by the ANSIINSF St<strong>and</strong>ard<br />
50 for Commercial fi lters.<br />
82