DRAINS<br />

Pools shall be equipped with at least two main drains, located in the deepest portion, at least 900<br />

mm apart. The drains have to be constructed in such a way to prevent suction entrapment under all<br />

operating conditions. An anti-vortex or an approved grate that has a minimum diagonal measurement<br />

of 600 mm, has safe openings of at least four times the area of the drain pipe <strong>and</strong> is securely fi xed into<br />

position to ensure that they are not readily removable by bathers, must cover each drain.<br />

Drains have to be spaced at interval of not exceeding 6.0 metres <strong>and</strong> may not be less more than 1.50<br />

metres from each side wall.<br />

In addition to the above, no check valve may be installed between a suction outlet <strong>and</strong> a pump.<br />

FLOW METER<br />

All public swimming pools must be equipped with fl ow metres that measure the rate of backwash<br />

through the fi lter. The fl ow meter shall be installed between the pump <strong>and</strong> the fi lter on a straight section<br />

of pipe in accordance with the manufacturer’s instructions, in a location where it may easily read. The<br />

meter shall measure the fl ow in litres per second <strong>and</strong> shall be accurate to within 5 % under all fl ow<br />

conditions. The fl ow meter shall further have an indicator that is capable of readings of at least 150 %<br />

of the normal fl ow rate.<br />

SIGHT GLASS<br />

Pressure fi lters systems shall have a sight glass fi tted on the waste discharge pipe.<br />

AIR RELIEF VALVES<br />

Pressure type fi lters shall be equipped with a means to release internal pressure. Each pressure fi lter<br />

shall be equipped with an air relief piping system connected at an accessible point near the crown.<br />

Automatic air relief systems may be used instead of manual systems.<br />

The design of a fi lter with an automatic air relief system as its principal means of air release shall<br />

include lids that provide a slow <strong>and</strong> safe release of pressure.<br />

The design of a separation tank used in conjunction with a fi lter tank shall include a manual means of<br />

air release or a lid that provides a slow <strong>and</strong> safe release of pressure as it is opened.<br />

ACCESS TO EQUIPMENT<br />

All of the above equipment (including all fi ltration equipment) has to readily accessible for inspection,<br />

maintenance <strong>and</strong> replacement purposes.<br />

FILTRATION<br />

Swimming<br />

The maximum fi ltration rate shall not exceed the design fl ow rates prescribed by the ANSIINSF St<strong>and</strong>ard<br />

50 for Commercial fi lters.<br />