Drive modules<br />

3.<br />

DRIVE MODULES<br />

Modular drives<br />

188<br />

DDS<br />

HARDWARE<br />

Ref.1209<br />

126<br />

Function of the connectors<br />

Power connector<br />

The power connectors located on top of each drive module are used to<br />

connect the motor.<br />

The ground connection of the cable shields in made from the vertical plate<br />

next to the connectors.<br />

The power bus input is located at the bottom of the modules and under<br />

the screwed-on lid. The drive needs 456-800 V DC which can vary depending<br />

on the mains voltage and the load. The power supply module is<br />

in charge supplying this voltage.<br />

2 plates are supplied with each module for this connection and another<br />

one for connecting the chassis with each other.<br />

The following table shows the values for gap, tightening torque, pole sections<br />

(wire entry holes) and other data regarding these screw-on connectors<br />

according to drive model:<br />

T. H3/6 Technical data of the terminals of the power connector.<br />

AXD/SPD/MMC 1.08<br />

1.15<br />

Connector data<br />

1.25 1.35 2.50<br />

2.75<br />

2.85 3.100<br />

3.150<br />

3.200<br />

3.250<br />

Gap (mm) 7.62 7.62 10.16 10.16 10.16 ---- ----<br />

Min/max tightening torque (Nm) 0.5/0.6 0.7/0.8 1.2/1.5 1.7/1.8 1.7/1.8 6/8 15/20<br />

Screw thread M3 M3 M4 M4 M4 M6 M8<br />

Min./max. section (mm²) 0.2/4 0.2/6 0.75/6 0.75/16 0.75/16 16/50 35/95<br />

Rated current In (A)<br />

Wire data<br />

20 41 41 76 76 150 232<br />

Length to strip (mm) 7 10 12 12 12 24 27<br />

WARNING. When connecting the drive module with its corresponding motor<br />

connect terminal U of the drive module with the terminal corresponding<br />

to the U phase of the motor. Proceed the same way to connect the<br />

terminals V-V, W-W and PE-PE. If they are not connected like this, it<br />

could perform poorly. The cable must have a metallic shield that must be<br />

connected to the ground terminal of the drive and to that of the motor in<br />

order to comply with EU directives.<br />

WARNING. Observe that before handling these terminals, you must proceed<br />

as indicated and in the following order:<br />

Disconnect the mains voltage at the electrical cabinet.<br />

Wait a few minutes before handling these terminals.<br />

The power supply needs time to decrease the voltage of the power bus<br />

down to safe values (< 42 V DC). The green indicator DC BUS ON being<br />

turned OFF does not mean that the power bus may be handled or manipulated.<br />

The discharge time depends on the number of elements connected<br />

and it is about 4 minutes.<br />

WARNING. Please note that the STO (Safe Torque Off) safety function<br />

does not imply an electrical power off. There is still voltage at the DC bus.<br />

Ignoring this warning may cause electric shock.