Power supplies<br />

2.<br />

POWER SUPPLIES<br />

94<br />

42<br />

Non-regenerative power supplies<br />

DDS<br />

HARDWARE<br />

Ref.1209<br />

Power connectors<br />

Terminal strip for mains connection<br />

When connecting the power supplies to mains through terminals L1, L2<br />

and L3, the phases may be connected in any order.<br />

FROM MAINS<br />

N<br />

R S T<br />

L1<br />

L2<br />

L3<br />

L1 L2 L3<br />

F. H2/8<br />

Terminal strip for connection to mains.<br />

The RST phases<br />

may be connected<br />

in any sequence.<br />

Cable without connectors<br />

MPC -4x ... (mm² )<br />

The ground connection of the cable shield is made from the vertical plate<br />

next to the terminal strip.<br />

The following table shows the values for gap, tightening torque (wire entry<br />

holes) and other data regarding these power screw-on terminals:<br />

T. H2/8 Technical data of the mains connection terminals.<br />

Connector data PS-25B4 PS-65A<br />

Gap (mm) 10.16 -<br />

Min/max tightening torque (N·m) 1.2/1.5 6/8<br />

Screw thread M4 M6<br />

Min./max. section (mm²) 0.5/16 16/50<br />

Rated current In (A) 76 150<br />

Wire data<br />

Length to strip (mm) 10 24<br />

MANDATORY. As for possible high leak currents, use a protection ground<br />

wire with a cross section of at least 10 mm² (Cu) or 16mm² (Al) or two<br />

protection ground wires with the same cross section as that of the wires<br />

connected to the power supply terminals. Comply with local regulations on<br />

grounding.<br />

MANDATORY. The equipment must be protected with fuses on the threephase<br />

supply lines L1, L2 and L3. Follow the instructions given in chapter<br />

6. POWER LINE CONNECTION of this manual.