Ohm values<br />

WARNING. The Ohm value of the external Ballast resistor must be the<br />

same as that of the internal resistor of that module.<br />

See the tables in section "resistor modules" of chapter 4 that show the<br />

compact drives and the possible external Ballast resistors associated with<br />

them.<br />

MANDATORY. On all compact drives (except those whose reference is<br />

SCD-NR x.xx), the external resistor supplied with the units.<br />

ACD/SCD/CMC 1.08 /1.15 models are also an exception.<br />

On compact drives "ACD/SCD/CMC 1.08/1.15", as opposed to the rest of<br />

the compact models, do not install any external Ballast resistor. The internal<br />

one is enough, except on "SCD 1.15" models where it would be possible<br />

to install the internal resistor ER+TH-43/350 if the application so<br />

required.<br />

In general, on compact models "ACD/CMC 1.08/1.15" the internal dissipation<br />

Ballast resistor will be enough, but if it is not in a particular situation, it<br />

is possible to install an external resistor of the same Ohm value as the internal<br />

one and greater dissipation power.<br />

Note. Actually, the external resistor provided with the unit is considered<br />

enough for most applications. If it is not enough, install one of the same<br />

Ohm value and greater power.<br />

On any compact drive whose reference is SCD-NR x.xx no external Ballast<br />

resistor will supplied with the unit. The user will place the order for the<br />

external resistor required by the application with a <strong>Fagor</strong> representative.<br />

Remember that it must have the same Ohm value as the internal resistor<br />

of the module.<br />

Heat dissipation<br />

The external Ballast resistors can generate a great deal of heat. That's why,<br />

sometimes, depending on the temperature of the installation area, it may be<br />

necessary to evacuate the heat by means of fans.<br />

INFORMATION. If a fan is required due the conditions of the location<br />

where the resistor will be installed, remember that <strong>Fagor</strong> <strong>Automation</strong> offers<br />

external ballast resistors with fan.<br />

See an example with data on the temperatures reached in points of the<br />

top of the module and the effect of the fan:<br />

T. H8/3 Temperatures reached in the points defined earlier in the figure F.<br />

H8/18. *Temperature variation due to the effect of the fan (PAPST<br />

614). Temperature in °C (conversion: °F = 32 + 1.8 °C).<br />

Dissipated power (W) 734 896 1042 1400 1400 *<br />

Ambient temperature (°C) 25 22 24 24 24<br />

T1 (°C) 90 89 115 138 74<br />

T2 (°C) 157 170 185 217 113<br />

T3 (°C) 80 79 88 104 64<br />

T4 (°C) 60 68 72 82 46<br />

T5 (°C) 50 54 57 65 47<br />

T6 (°C) 40 40 44 45 44<br />

Installation<br />

INSTALLATION<br />

Connection between modules 8.<br />

DDS<br />

HARDWARE<br />

Ref.1209<br />

289