Connection of the control and communications signals<br />

312<br />

DDS<br />

HARDWARE<br />

Ref.1209<br />

308<br />

RS-422 serial line connection<br />

This communication interface may be set only between drive modules<br />

MMC or CMC and an ESA video terminal as a master element.<br />

The various drive modules and the ESA panel are connected through the<br />

RS-232/RS-422 serial port (connector X6) of the drive and the serial port<br />

of the video terminal (connector MSP).<br />

The RS-232/RS-422 serial port is implemented only on <strong>Fagor</strong> drives in<br />

motion control applications (see their front panel).<br />

The connection is made through the RS-232/RS-422 cable.<br />

See chapter 7. CABLES of this manual.<br />

It is a tree type connection where the 16-position rotary switch (0-15) of<br />

each drive permits selecting the address of each module integrated in it.<br />

The system communication through RS-232/RS-422 is configured using<br />

the WinddsSetup application for PC. See the "communications" tab of<br />

the menu in chapter 16. WinddsSetup of the "dds-software"<br />

manual.<br />

Particular<br />

In order to establish communication via RS-232 serial line, each drive of<br />

the system must be differentiated using the 16-position "NODE SELECT"<br />

switch. The direction of the arrow of the switch must coincide with an<br />

identifier other than zero, hence assigning a node number that will identify<br />

in the system.<br />

If the drive is going to be identified in the SERCOS ring with a number<br />

higher than 15 in a tree-like structure that has RS-422 communications<br />

line, this value cannot be selected using the rotary "NODE SELECT "<br />

switch because it only has 15 positions.<br />

Identifying the axes with addresses higher than 15 requires setting QP13.<br />

See this parameter in chapter 13 of the "dds-software" manual.<br />

Example.<br />

How to identify an axis addressed in position 26 in the system when communicating<br />

via RS-422 serial line ?<br />

When the identifier of the axis is higher than 15 (like in this case), QP13<br />

must be set so it meets the ratio:<br />

Defined Id = Id to be selected at the rotary switch + (15 x QP13).<br />

Hence, for defined Id=26, select C (same as 11) at the drive's rotary<br />

"NODE SELECT" switch and set QP13=1.<br />

In order to establish communication via RS-232 serial line, the direction of<br />

the arrow of the switch of the corresponding module must coincide with the<br />

zero identifier.<br />

The module must be reset in order for any change made on the rotary<br />

switch to be effective.<br />

Interconnection<br />

Use the RS-232/RS-422 cable to connect all the drives that will be governed<br />

by the video terminal. See chapter 7. CABLES of this manual.