Functional safety<br />

9.<br />

FUNCTIONAL SAFETY<br />

Maintenance, repair and analyze hazardous events<br />

326<br />

DDS<br />

HARDWARE<br />

Ref.1209<br />

324<br />

9.10 Maintenance, repair and analyze hazardous events<br />

Although it is not required due to its low probability, <strong>Fagor</strong> recommends to<br />

demand the STO safety function at least once every 24 hours in order to<br />

detect possible failures in the STO circuit.<br />

The external main contactor - KM1 and Drive Enable have electromechanical<br />

components that wear out in time. Their failures due to deterioration<br />

must be detected by the diagnostics of the safety controller.<br />

The test interval of the Drive Enable is the same as its useful life, i.e. 20<br />

years. After this period, the Drive Enable is no longer reliable.<br />

The useful life (mission) of the STO safety function is 20 years. After that<br />

time, the safety function will no longer be valid. The expiration date must<br />

be calculated by adding 20 years to the date shown on the version label<br />

of the unit. Write down this value in the maintenance plan of the installation.<br />

Do not use the safety function after that date.<br />

If the STO safety function has been implemented according to ISO 13849<br />

PL d (see examples in this chapter), the safety controller will detect an<br />

error at the Drive Enable reading AS1-AS2 or and error at external main<br />

contactor - KM1 with its feedback contact only when carrying out a demand<br />

of the STO.<br />

If the external main contactor - KM1 breaks down, it must be replaced.<br />

Repair<br />

Neither the user nor the OEM is authorized to repair any AXD/SPD<br />

modules, not even to replace boards.<br />

If the Drive Enable circuit breaks down, the AXD/SPD must be replaced<br />

and commissioning test and registering must be done again.