T. H5/14 Selection of the mains connection cable.<br />

POWER CABLE FOR MAINS CONNECTION<br />

Vmains from 400 to 460 V AC Rated current through the mains cable<br />

MAINS POWER<br />

4 (kW) * 1000 / (3 · Vmains) = A C<br />

COMPACT AXIS DRIVES (ACD):<br />

RATED CURRENT ON FXM & FKM MOTORS = A C<br />

COMPACT SPINDLE DRIVES (SCD):<br />

MAX. CURRENT ON FM7/FM9 MOTORS = A C<br />

Power cable<br />

In Amperes Reference<br />

if C < 12.5 MPC-4x1.5<br />

if C < 16.5 MPC-4x2.5<br />

if C < 23 MPC-4x4<br />

if C < 29 MPC-4x6<br />

if C < 40 MPC-4x10<br />

The purchase order must indicate the length of the cables<br />

<br />

Selection criteria<br />

SELECTING CRITERIA<br />

Power supply selection 5.<br />

DDS<br />

HARDWARE<br />

Ref.1209<br />