Power supplies<br />

2.<br />

POWER SUPPLIES<br />

94<br />

58<br />

Regenerative power supplies<br />

DDS<br />

HARDWARE<br />

Ref.1209<br />

Power connectors<br />

Terminal strip for mains connection<br />

When connecting the power supplies to mains, the phases may be connected<br />

in any order.<br />

FROM MAINS<br />

N<br />

R S T<br />

L1<br />

L2<br />

L3<br />

L1 L2 L3<br />

F. H2/19<br />

Terminal strip for connection to mains.<br />

The RST phases may<br />

be connected in any<br />

sequence<br />

Cable without connectors<br />

MPC-4x ... (mm² )<br />

The ground connection of the cable shield is made from the vertical plate<br />

next to the terminal strip.<br />

The following table shows the values for gap, tightening torque, sections<br />

and other interesting data of the power feed-through terminal blocks:<br />

T. H2/16 Technical data of the feed-through terminal blocks for mains<br />

connection<br />

Connector data XPS-25 XPS-65<br />

Min/max tightening torque (N·m) 2.0/2.3 6/8<br />

Screw thread M5 M6<br />

Min./max. section (mm²) 0.5/16 16/50<br />

Rated current In (A)<br />

Wire data<br />

76 150<br />

Length to strip (mm) 16 24<br />

MANDATORY. As for possible high leak currents, use a protection ground wire<br />

with a cross section of at least 10 mm² (Cu) or 16mm² (Al) or two protection<br />

ground wires with the same cross section as that of the wires connected to<br />

the power supply terminals. Comply with local regulations on grounding.<br />

MANDATORY. The equipment must be protected with fuses on the threephase<br />

supply lines L1, L2 and L3. Follow the instructions given in chapter<br />

6. POWER LINE CONNECTION of this manual.