ANNEX XXXXXIV (3 <strong>of</strong> 4)ESTATE FACILITIES DESIGN GUIDE- COMMERCIAL CENTRES BTG-CC-109ISSUE 114 JULY 1995DESIGN GUIDEBUILDING SERVICES3. FIRE SERVICESa) Compartmentatxon<strong>The</strong> system shall be installed in accordance with the Code <strong>of</strong>Practice for Minimum Fire Service Installations and Equipment.For the aggregate volume <strong>of</strong> any continuous compartment exceeding28,000 m3, segregation by means <strong>of</strong> fire roller shutter is normallyrequired. Construction <strong>of</strong> the shutter shall be carried out by theMain Contractor. <strong>The</strong> installation <strong>of</strong> the actuating devices, suchas fusible/electro-thermal link and smoke/heat detector, shall becarried out by the nominated F.S. sub-contractor. Refer toBuilding Services Engineering Manual DBFW.b) Sprinkler System i) Sprinkler system would normally be required and classified asOH III for a Commercial Centre and for a Carpark asstipulated in the Loss Prevention Council (LPC) Rules,ii) <strong>The</strong> sprinkler tank is recommended to be located on the ro<strong>of</strong>and with a booster pump system. If the water supply to thero<strong>of</strong> tank cannot be directly fed, a sump and pump system isrequired. Allowance should be made to cater for theinstallation <strong>of</strong> an additional layer <strong>of</strong> sprinkler points byspecial shops tenants.iii)For market, provision <strong>of</strong> two layers <strong>of</strong> sprinkler points shouldbe considered, one layer for the ceiling void <strong>of</strong> market stallsand the other below airducts in common areas/below stallcockl<strong>of</strong>ts.iv) Drop pipes and associated valves leading to the othersprinkler layer should be installed at high level <strong>of</strong> commonareas for ease <strong>of</strong> servicing and maintenance.v) <strong>The</strong> PA shall check whether the system will be fed from thetown main at both ends.vi) It is recommended that the sprinkler installation for specialshops (e.g. Chinese Restaurant and Car Park) shall beseparately zoned and operated by a separate set <strong>of</strong> controlvalve.c) Fire DetectionSystemAn automatic fire alarm (AFA) system with direct telephone lineconnection and separate zoning and control is required.d) Fire Hydrant, HoseReel, PortableAppliances<strong>The</strong>se systems shall be provided in conspicuous locations along theshopping arcade as well as inside market and special shop unit.All fire hydrants, hose reels and portable appliances shallpreferably be installed in an enclosure.Portable appliancesSand Buckets. • Water/CO 2FoamFire blanketno. as required9 Litres9 LitresNon-asbestos typePage 11 <strong>of</strong> 31

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!