4. 10. 2. Fire<br />

2 1 /2 inches. Fire hydrants shall be capable <strong>of</strong> providing a required fire flow <strong>of</strong><br />

60,000 gallons per minute at 20 pounds per square inch residual pressure for a<br />

five-hour duration. The distance between hydrants shall not exceed 250 feet, and<br />

the maximum travel distance along a roadway frontage shall not exceed 150 feet.<br />

Hydrants shall be placed in the parking area under the same regulations.<br />

3. All structures in the Project Area shall be protected by separate combined<br />

standpipe systems, including automatic fire sprinkler systems, designed to the<br />

standards established by the <strong>Glendale</strong> Fire Division. Adequate on-site water<br />

supply shall be capable <strong>of</strong> supplying fire protection systems for a period <strong>of</strong> 30<br />

minutes and shall be used for fire protection purposes only. Fire protection<br />

systems shall be zoned to provide proper pressures for operations at any level <strong>of</strong><br />

the structure.<br />

4. Each fire control room shaH be accessible directly from the outside and readily<br />

accessible for emergency responders. The room shall not be used for other<br />

purposes and shall be sized in accordance with Fire Division requirements.<br />

5. Smoke control and removal shall be accomplished through mechanical means<br />

designed in accordance with methods approved by the <strong>Glendale</strong> Fire Division.<br />

6. The fire alarm system must utilize a graphic-type annunciator to provide rapid<br />

response by emergency equipment and personnel who may be unfamiliar with the<br />

structure.<br />

7. Emergency electrical power shall be provided to power all emergency equipment<br />

including, but not limited to, fire alarms, fire pumps, emergency lighting,<br />

elevators, and smoke control fans. Emergency power shall be capable <strong>of</strong><br />

providing power to all emergency equipment for a period <strong>of</strong> eight hours <strong>of</strong><br />

continuous use.<br />

8. The project's parking facilities shall be approved by the <strong>Glendale</strong> Fire Division<br />

for parking adjacent to all structures to determine proper access to all parts <strong>of</strong><br />

the structure.<br />

9. All structures may be required to have Fire Division access on a minimum <strong>of</strong><br />

two sides. Fire Division connections serving the combined standpipe system<br />

shall be provided and accessible along each access roadway. Additionally, each<br />

floor shall have breakable windows with the appropriate indicating signs affixed.<br />

All breakable windows shall be constructed <strong>of</strong> tempered glass.<br />

PlaMing Consultants Research<br />

<strong>Glendale</strong> Redevelopment Agency<br />

Page 92<br />

DreamWorks Animation Campus Addendum ErR<br />

June 1996