5.10.2.2.1 ENERGY TAGS<br />
The following tags are available for energy management:<br />
LI1..LI8 Latched input<br />
General Reference Guide IO Servers Configuration<br />
Figure 91: <strong>eWON</strong> IO server default parameters<br />
REM1: Energy tags are logged after each new period IF Logging is enabled, even if the value has not changed since previous period.<br />
REM2: Even if Deadband is -1 and Interval is 0. If not, you will have additional points and even maybe duplicate points.<br />
(*) Important: See “Tags are stored as Float” on page 67<br />
5.10.2.2.2 32 BIT COUNTER TAGS:<br />
When the Integration Period expires, the number of pulses counted during the integration<br />
period are logged in the corresponding LIx.<br />
ST1..ST4 Status variables:<br />
ST1 This is the absolute time when counter were latched.<br />
Expressed in seconds since 1/1/1970 minus 0x30000000 HEX (or 805306368 decimal).<br />
Latch time - 0x30000000<br />
This huge value is substracted to maintain precision in the Float storage. (*)<br />
ST2<br />
Period status<br />
ST3<br />
Period length sec<br />
ST4<br />
Period Num<br />
0 means period is valid (within tolerance), 1 means period is invalid.<br />
Length of the period in second.<br />
This 32 bit counter counts is increased by 1 after each integration period. It can be used with<br />
ONCHANGE to perform operations when period expires.<br />
The <strong>eWON</strong> IO Server provides now 8 32 bits (*) counter tags named: CI1..CI8. These counters are writable but writing in these registers affects<br />
the LIx inputs of the Energy IO server module.<br />
(*) Important: See “Tags are stored as Float” on page 67<br />
RG-001-0-EN ver 1.6 <strong>eWON</strong>® - 22/06/2009 - ©ACT'L sa Page 120