General Reference Guide <strong>eWON</strong> Configuration<br />

• Historical and real-time logging:<br />

Those fields display only for some <strong>eWON</strong>'s versions (c.f. “Tags monitoring and handling” on page 68)<br />

Historical logging enabled<br />

3.4.2.1.1 Publish as Modbus TCP<br />

This feature allows to access a Tag Value through Modbus/TCP. In that configuration, the <strong>eWON</strong> acts as a slave. Actually, there is no data map<br />

as in most PLC, instead of that you define Tag by Tag its Modbus TCP address.<br />

3.4.2.1.1.1 Defining the Modbus TCP address<br />

There are 4 types of Modbus variable, Contact (RO), Coil (RW), Input Register (RO), Holding register (RW). The type selected for the Tag that<br />

you want to publish will depend on its type:<br />

Usually, the RO or RW property of a Tag is obvious. But in case of doubt, you can confirm the type by checking the View IO for the Tag:<br />

• Remove the "Force Read Only" option in the Tag configuration (disabled by default).<br />

• Check the View IO page, if the Tag has an update field, it means it is a RW Tag otherwise the Tag is RO.<br />

• The address selected will be the address of the Modbus 16 bit register. The address range starts with register 1 (in the Modbus frame,<br />

<strong>eWON</strong> register 1 is transmitted as 0).<br />

• Publish as float<br />

The <strong>eWON</strong> supports accessing Tag values as float registers. The float is published with the IEEE representation and the value can be read on 2<br />

consecutive registers, with the first register starting at the user defined address.<br />

3.4.2.1.1.2 Modbus TCP rules<br />

Historical and real-time logging<br />

If checked, the Tag values will be logged in a circular file.<br />

Warning: This is a non-volatile logging; data are stored in the flash file system. All the data are stored in<br />

the same file, the maximum number of values that can be saved is from 16384 to 139264, depending on<br />

the way you have set up the resources storage in the <strong>eWON</strong> (when maximum size is reached, then the<br />

older data will be erased first).<br />

If one Tag “a” is recorded very often (every seconds) and another Tag “b” is recorded rarely (every day),<br />

you may have your Historical Log filled with a lot of tag “a” and few (or none) tag “b” because of the<br />

circular storage mechanism.<br />

Logging dead band Defines the dead band of the Tag’s incremental recording (use a negative value to disable it)<br />

Logging Interval<br />

Real time enabled<br />

Defines the interval, in seconds, for the Tag recording (set to zero to disable the logging interval).<br />

Can be used at the same time as logging dead band.<br />

If checked, the Tag values will be logged in memory.<br />

Real time logging is different from historical logging because data are saved in a circular memory buffer.<br />

The other difference with historical time logging is that incremental recording is not possible, only fixed<br />

interval recording can be performed.<br />

Time span Defines the total logging window time in seconds.<br />

Logging Interval Defines the interval, in seconds, of the Tag recording<br />

Table 48: Historical and real-time logging controls<br />

Tag property Modbus data type<br />

Boolean, RO Contact<br />

Boolean, RW Coil<br />

Analog, RO Input register<br />

Analog, RW Holding register<br />

Table 49: the 4 Modbus variable types<br />

• When accessing Modbus registers or coils that are not mapped to an <strong>eWON</strong> register, the returned value is 0.<br />

• Maximum number of registers readable in 1 request: 25<br />

• Maximum number of coils readable in 1 request: 2000<br />

RG-001-0-EN ver 1.6 <strong>eWON</strong>® - 22/06/2009 - ©ACT'L sa Page 74