5.13 S7-200 (PPI - ISOTCP)<br />
5.13.1 Introduction<br />
General Reference Guide IO Servers Configuration<br />
The S7200 IO Server is dedicated to communicate directly with SIEMENS PLC of family S7-200.<br />
The <strong>eWON</strong> will connect directly to the PLC’s PPI interface.<br />
Since firmware 5.5, <strong>eWON</strong>s with an MPI port are able to communicate on a PPI MultiMaster bus.<br />
Then, to communicate with a S7-200 device you could use either an <strong>eWON</strong> with a serial port or an <strong>eWON</strong> with an MPI port.<br />
The <strong>eWON</strong> acts always as MASTER.<br />
The standard serial port of <strong>eWON</strong> must be configure in RS-485 (with dipswitch) to communicate in PPI.<br />
The ISOTCP (Ethernet) is available on all the <strong>eWON</strong> types.<br />
5.13.2 Setup<br />
5.13.2.1 Gateway configuration<br />
Usage<br />
MonoMaster<br />
<strong>eWON</strong> is the ONLY Master on the PPI network.<br />
MultiMaster<br />
<strong>eWON</strong> is not the only Master on the PPI network.<br />
Other masters (HMI or PPI multimaster programming cables)<br />
may be present at the same time on the PPI bus.<br />
5.13.2.2 COM configuration (serial port)<br />
<strong>eWON</strong> with SERIAL port<br />
(EWxxx0x)<br />
Figure 99: Gateway parameters<br />
<strong>eWON</strong> with MPI port<br />
(EWxxx6x)<br />
RG-001-0-EN ver 1.6 <strong>eWON</strong>® - 22/06/2009 - ©ACT'L sa Page 130<br />
Yes<br />
No<br />
Table 106: PPI MonoMaster/MultiMaster usage<br />
Parameter Description<br />
Destination PPI Address Identifies the PLC PPI Destination address when ISOTCP is used<br />
Yes<br />
(since firmware 5.5)<br />
Yes<br />
(since firmware 5.5)