7 Retrieving Data from <strong>eWON</strong><br />

7.1 List of <strong>eWON</strong> files<br />

General Reference Guide Retrieving data from <strong>eWON</strong><br />

The <strong>eWON</strong> flash file system contains the following files (R: read, W: write). Detailed information about files format are contained in the Technical<br />

Notes that you can download from the <strong>eWON</strong> web site (<strong>Support</strong>/Documentation/Technical notes on http://support.ewon.biz):<br />

• TN02: <strong>eWON</strong> files format<br />

• TN03: ircAll.bin format<br />

• TN12: var_lst.txt format<br />

File Name Type Description<br />

Events.htm R <strong>eWON</strong> events occurred (as log in, log out, error) - html format<br />

sstat.htm R All the scheduled actions status for the current session - html format<br />

estat.htm R Current status of the <strong>eWON</strong> - html format<br />

rt_alm.txt R Real time alarms list<br />

inst_val.txt R/W Contains the instant values from the Tags that have been defined in <strong>eWON</strong> - text format<br />

inst_val.bin R/W Instant values from <strong>eWON</strong>'s Tags - binary format<br />

events.txt R <strong>eWON</strong> events occurred (as log in, log out, error) - text format<br />

hst_alm.txt R Historical alarms list - text format<br />

var_lst.txt R/W List of all the <strong>eWON</strong> Tag names which are logged - text format<br />

var_lst.csv R/W List of all the <strong>eWON</strong> Tag names which are logged (csv format)<br />

program.bas R/W The whole source code of <strong>eWON</strong> basic program<br />

ewonfwr.edf W <strong>eWON</strong>'s firmware file<br />

dump.ppp R ppp dump file (can be analyzed by using a software that manages the .ppp format)<br />

config.bin R/W <strong>eWON</strong> configuration - binary format<br />

config.txt R <strong>eWON</strong> configuration - text format<br />

comcfg.txt R <strong>eWON</strong> COM configuration - text format<br />

ircall.bin R All the binary values from all Tags that have been defined in <strong>eWON</strong><br />

icr_XXXXX.txt R<br />

Incremental recording file.<br />

One file per each of the Tags that are listed inside the var_lst.txt file<br />

remote.bas W Single shot execution section (max size = 3000 bytes)<br />

backup.tar R/W<br />

data.tar R/W<br />

Archive containing all necessary files to backup the <strong>eWON</strong>.<br />

config.txt, comcfg.txt, program.bas and /usr directory (with subdirs).<br />

When the archive is written, the <strong>eWON</strong> is firstly cleared before applying the all files.<br />

Archive containing all necessary files to backup the <strong>eWON</strong>.<br />

config.txt, comcfg.txt, program.bas and /usr directory (with subdirs).<br />

When the archive is written, the <strong>eWON</strong> is not cleared before applying the all files.<br />

Table 136: <strong>eWON</strong> files list<br />

• Files ewonfwr.edf and config.bin are binary files and cannot be modify by users. The config.bin file is Read/Write to allow users to<br />

"copy/paste" configuration from one <strong>eWON</strong> to another.<br />

• The program.bas file is Read/Write; this allows you to design your program offline with your text editor and to upload it to the <strong>eWON</strong>.<br />

• Remote.bas is not readable. When a remote.bas (max size = 3000 bytes) file is "dropped" in the <strong>eWON</strong> root directory, this program is<br />

executed 1 time. This feature can be used to execute a single shot action in an automated way.<br />

RG-001-0-EN ver 1.6 <strong>eWON</strong>® - 22/06/2009 - ©ACT'L sa Page 164